The gas pipeline can be brought in through the right or left side of 

the appliance. The insert has a Flexline with shutoff valve located 

on the right side when facing the unit. 

See Figures 5 and 6.

  Consult 

the current National Fuel Gas Code, ANSI Z223.1 CAN/CGA-B149 

(.1 or .2) installation code.

Installing the Main Gas Cock

Each appliance should have its own manual gas cock.

A manual main gas cock should be located in the vicinity of the 

unit. Where none exists, or where its size or location is not ad-

equate, contact your local authorized installer for installation or 

relocation.

Compounds used on threaded joints of gas piping shall be resistant 

to the action of liquefied petroleum gases. The gas lines must be 

checked for leaks by the installer. This should be done with a soap 

solution watching for bubbles on all exposed connections, and if 

unexposed, a pressure test should be made. 

Never use an exposed flame to check for leaks. Appliance must 

be disconnected from piping at inlet of control valve and pipe 

capped or plugged for pressure test. Never pressure test with 

appliance connected; control valve will sustain damage!
NOTE: 

The millivolt gas controls are equipped with a captured 

screw type pressure test point, therefore it is not necessary to provide 

a 1/8" test point up stream of the control.
When using copper or flex connector use only approved fittings. 

The appliance and it’s individual shut off valve must be disconnected 

from supply piping system during any pressure testing of that system 

at test pressures in excess of 1/2 psig (3.5kPa).

The appliance must be isolated from the gas supply piping system 

by closing its individual manual shut off valve during any pressure 

testing of the gas supply piping system at test pressures equal to or 

less than 1/2 psig (3.5kPa).

Attention!

 If one of the procedures results in pressures in excess 

of 1/2 psig (14" w.c.) (3.5 kPa) on the fireplace gas valve, it will 

result in a hazardous condition.

Checking Manifold Pressures

Both  Propane  and  Natural  gas  valves  have  a  built-in  pressure 

regulator in the gas valve. Natural gas models will have a manifold 

pressure of approximately 3.5" w.c. (.871kPa) at the valve outlet 

with the inlet pressure to the valve from a minimum of 4.5" w.c. 

(1.120kPa) for the purpose of input adjustment to a maximum of 

14.0" w.c. (3.484kPa). Propane gas models will have a manifold 

pressure approximately 10.0" w.c. (2.49kPa) at the valve outlet 

with the inlet pressure to the valve from a minimum of 10.8" w.c. 

(2.68kPa) for the purpose of input adjustment to a maximum of 

14.0" w.c. (3.484kPa).  

Gas Supply Pressure (inches w.c.)

Minimum Normal

Maximum

Natural Gas

4.5"

7.0"

14.0"

LP (Propane)

10.8"

11.0"

14.0"

Manifold Pressure (inches w.c.)

Normal (HI)

Natural Gas

3.5"

LP (Propane)

10.0"

Note:

 Never use plastic pipe. Check to confirm whether your 

local codes allow copper tubing or galvanized.

Note:

 Since some municipalities have additional local codes, it is 

always best to consult your local authority and installation code.
The use of the following gas connectors is recommended:
—  ANS Z21.24 Appliance Connectors of Corrugated Metal Tubing 

and Fittings.

—  ANS  Z21.45 Assembled  Flexible Appliance  Connectors  of 

Other Than All-Metal Construction

The above connectors may be used if acceptable by the authority 

having jurisdiction. The state of Massachusetts requires that a flexible 

appliance connector cannot exceed three feet in length.

Recommended Gas Pipe Diameter

Pipe Length

Schedule 40 Pipe 

Inside Diameter

Tubing, Type L

Outside Diameter

Nat.

L.P.

Nat.

L.P.

0-10ft

0-3m

1/2"

12.7mm

3/8"

9.5mm

1/2"

12.7mm

3/8"

9.5mm

11-40ft

4-12m

1/2"

12.7mm

1/2"

12.7mm

5/8"

15.9mm

1/2"

12.7mm

41-100ft

13-30m

1/2"

12.7mm

1/2"

12.7mm

3/4"

19mm

1/2"

12.7mm

101-150ft

31-46m

3/4"

19mm

1/2"

12.7mm

7/8"

22.2mm

3/4"

1.9 mm

GAS SUPPLY

GAS FLEX LINE WITH

SHUTOFF VALVE

(PROVIDED)

FRONT OF

INSERT

RIGHT SIDE OF INSERT

Figure 6

Содержание DV25IN33L-1

Страница 1: ...iance is not convertible for use with other gases unless a certi ed kit is used GAS FIRED Installer Leave this manual with the appli ance Consumer Retain this manual for future refer ence Do not store...

Страница 2: ...10 12 Vertical Termination 13 Alternate ON OFF Switch Installation 14 Surround Panel Installation 15 Blower Accessory Information 16 Log Placement 17 Operating Instructions 18 Standing Pilot Lighting...

Страница 3: ...t clean Vent cap is hot while replace is in operation Installation and repair should be done by a QUALIFIED SERVICE PERSON The appliance should be inspected before use and at least annually by a quali...

Страница 4: ...perform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorption on wal...

Страница 5: ...ng jurisdiction State of Massachusetts The installation must be made by a licensed plumber or gas tter in the Commonwealth of Massachusetts The installation must conform with local codes or in the abs...

Страница 6: ...talling to an existing round replace chimney pipe DVVK3FV Vertical Vent Kit 25 Two pieces of 25 FlexVent Rectangle Cap Flashing connectors and clamps Recommended when installing to a square or rectang...

Страница 7: ...28 14 1 2 11 1 8 25 1 4 12 3 4 17 18 5 16 27 6 3 4 9 20 25 5 8 40 DV33IN 22 3 4 31 16 14 1 8 28 1 4 14 1 4 18 3 4 21 5 16 30 8 1 4 10 1 2 21 1 2 28 5 8 43 DV35IN 24 3 4 34 16 16 1 8 31 1 4 14 1 4 21 3...

Страница 8: ...10 1 3 4 23 11 Combustible Material No greeting cards stockings or ornamentation of any type should be placed on or attached to the replace The ow of heat can ignite combustibles Figure 4 8 MINIMUM CL...

Страница 9: ...s results in pressures in excess of 1 2 psig 14 w c 3 5 kPa on the replace gas valve it will result in a hazardous condition Checking Manifold Pressures Both Propane and Natural gas valves have a buil...

Страница 10: ...sting air circulation vents or grills NOTE Cutting of sheet metal parts of a replace in order to install the replace insert is prohibited WARNING Only the surround as supplied may be used to cover int...

Страница 11: ...asonry chimney may need to be removed to allow installation of the exible vent pipe When installing into a zero clearance factory built wood burning replaces the use of the DVKI Round Vertical Termina...

Страница 12: ...NT CONNECTION RETAINER SCREWS MAY BE INSTALLED THROUGH THE VENT CLAMPS TO ENSURE POSITIVE SECUREMENT OF VENTING SCREWS ADDED THROUGH VENT CLAMPS TO RETAIN VENTING TO COLLARS RECOMMENDED USE HIGH TEMP...

Страница 13: ...ly dripping out at joints or seams Condensate can cause corrosion of caps pipe and ttings It may be caused by having excessive lateral runs or having exterior portions of the system exposed to cold we...

Страница 14: ...ound panel assembly against the face of the insert and align the lower retaining tabs with the notches on the insert sides Lift the surround panel assembly slightly until the bottom return ange top pa...

Страница 15: ...FINISHING THE FIREPLACE INSERT NEVER OBSTRUCT OR MODIFY THE AIR INLET OUTLET LOUVERS ON THE FIREPLACE IN SERT IN ANY MANNER NOTE INSTALL SURROUND PANELS SO THAT THE TOP PANEL RETURN FLANGE SLIDE S OV...

Страница 16: ...nd BTU input level setting control by adjustment of the HI LO knob located on the gas valve Blower removal instructions Servicing or removal of the blower system must be performed by a quali ed servic...

Страница 17: ...support Note DV25IN models incorporate two small tabs in the rear log support that keep the back log positioned correctly DV33IN models have one small tab in the rear log support to ensure the back lo...

Страница 18: ...N position This time period allows the millivolts electrical current to build up to a suf cient level allowing the gas control to operate properly 1 Follow the SAFETY and LIGHTING INSTRUCTIONS for sta...

Страница 19: ...switch to desired setting FOR YOUR SAFETY READ BEFORE LIGHTING WARNING If you do not follow these instructions exactly a re or explosion may result causing property damage personal injury or loss of l...

Страница 20: ...ptional Wall Switch Position the wall switch in the desired position on a wall Run a maximum of 25 feet 7 8m or less length of 18 A W G minimum wire and connect it to the replace valve pigtails WARNIN...

Страница 21: ...s from the thermopile at the gas valve terminals are tight and the thermopile is fully inserted into the pilot bracket Check the thermopile with a millivolt meter Take the reading atTH TP TPterminals...

Страница 22: ...that no debris is interfering with the ow of air Inspect entire vent system for proper function Cleaning Logs Use a soft brush attachment on a vacuum cleaner to gently remove dust or soot deposits fr...

Страница 23: ...what your dealer can furnish contact Empire Comfort Systems Inc Nine Eighteen Freeburg Ave Belleville Illinois 62220 Black Gold Finish Hammered Pewter Brushed Stainless Black Gold Finish Hammered Pewt...

Страница 24: ...23015 6 0408 Page 24 INSERT PARTS VIEW 1 2 3 4 5 6 7 8 9 10 11 13 14 15 16 17 19 20 21 22 23 24 25 26 27 28 29 30 31 33 34 35 36 37 38 39 40 41 7 12 32 42 43 18 44 45 46 48 47 49...

Страница 25: ...23a P286 P270 P244 ORIFICE MAIN BURNER NAT 23b P214 P210 P245 ORIFICE MAIN BURNER LP 24 23311 23017 23017 BURNER ASSEMBLY 25 22959 22959 22959 VALVE BRACKET 26 22739 22738 22738 TUBING ASSEMBLY 27 22...

Страница 26: ...ne the Part Number not the Index Number and the Description of each part from the following appropriate illustration and list Be sure to give all this information Fireplace Number Part Description Fir...

Страница 27: ...23015 6 0408 Page 27 SERVICE NOTES...

Страница 28: ...s Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question...

Отзывы: