Page 24
ecom-B
6.3. Diagnosis gas
Select from the main menu the sub menu
“Diagnosis Gas”
and
press
<Enter>
. The table of fuel types will be displayed. Following
fuel types can be selected:
Natural gas (B)
Town gas (B)
Coke gas (B)
Liquid gas (B)
Select with the arrow keys the correspond-
ing fuel type and confirm by pressing
<En-
ter>
.
First the thermal capacity brought to the
boiler can be determined with the ecom-B.
For this the gas meter has to be observed.
By pressing
<Enter>
a stopwatch can be
started and stopped. The amount of gas
consumed in the meantime is necessary
for calculation and is entered as follows:
1. Select the position which should be
changed with the keys
<store>
(left) and
<Print>
(right) (corresponding field flashes)
2. Set the value by using the cursers
<up /
down>
.
After setting and confirmation by pressing
<Enter>
the result of the calculation will be
displayed and stored. Calculation can be
repeated if needed. For calculation follow-
ing heating values are taken:
Natural gas (B) = 9,53 kWh/m
3
Town gas (B) = 5,00 kWh/m
3
Coke gas (B) = 4,83 kWh/m
3
Liquid gas (B) = 25,90 kWh/m
3
Type of fuel
Natural gas (B)
CO2max : 11.8
A1-fact. : 0.37
Select with
↑↓
Diagnosis gas
Gas flow rate
- - . -
m3/h
Perfo.
- - . -
kW
Start :
↵
↵↵
↵
Diagnosis gas
Gasdurchsatz
2.0
m3/h
Perfo.
19.1
kW
Start :
↵
↵↵
↵
Diagnosis gas
Gas flow rate
Time:
1
sec
Continue with :
↵
↵↵
↵
Diagnosis gas
Gas flow rate
0
.100
m3
↑↓
↵
↵
↵
↵ ← →
Содержание B
Страница 1: ...Operating Instructions ...