Mounting and operating instructions
9.1.2
Operating
9.1.3
Safety elements
9.1.4
Feeding
No.
Description
Cause
Elimination
Checking time
Reaction
E20
01
SER Test
SER Test signal unsuccessful.
SER short-circuit to the earth.
Check the cabling of the sensor or the
jumper.
Prior to closing.
A
02
SER too slow.
SER reacts too slowly.
Check the cabling of the sensor.
Check for polarity reversal/test signal.
E21
01
SES Test
SES Test signal unsuccessful.
SES short-circuit to the earth.
Check the cabling of the sensor or the
jumper.
Prior to opening.
A
02
SES too slow.
SES reacts too slowly.
Check the cabling of the sensor.
Check for polarity reversal/test signal.
E22
01
EMY Test
EMY input on 24 V.
Check the jumper EMY.
Check the cabling of EMY.
Permanent.
H
No.
Description
Cause
Elimination
Checking time
Reaction
E30
01
30 V Error
30 V too low.
Mains failure, overload motor. Check the feed-in.
Replace the hardware.
Permanent.
A
02
30 V too high.
03
Error upon switching-on.
E31
01
24 V General
Error upon switching-on.
Overload, short-circuit 24 VDC onto terminals
X101, X102 or X116 (Fire protection PCB/Relay
PCB).
Permanent.
A
Restart after 10 s.
02
Over- resp. under-voltage.
E32
01
24 V Safety
Over- resp. under-voltage.
Overload, short-circuit 24 VDC onto terminals
X105 or X107.
E33
01
24 V E-Lock
Error:
Over- resp. under-voltage.
Overload, short-circuit 24 VDC onto terminal X108.
02
Premonition:
Over- resp. under-voltage.
E34
01
24 V CAN
Over- resp. under-voltage.
Overload, short-circuit external power supply CAN.
No.
Description
Cause
Elimination
Checking time
Reaction
E10
01
Fullteach required Parameter Ao, Rod, Invers or
dAxis changed.
Carry out a teach.
Upon changing the
drive mechanism
configuration.
H
02
Minimum opening angle has not
been reached.
Check the locking/electric lock.
During Teach.
H
E11
01
Halfteach required
(Opening)
Parameter Vo changed.
Carry out a complete and unhindered
opening cycle.
Upon changing the
motional parameters.
W
02
Halfteach required
(Closing)
Parameter Vc or FSlam changed.
Carry out a complete and unhindered
closing cycle.
E12
03
Excessively high
current con
-
sumption during
Teach in the open
position (> 5 A)
Drive unit pushes against the
open position stop piece or an
obstacle. The spring tension is
possibly too high.
Reduce the opening angle Ao.
Reduce the spring tension.
Open position Teach 3
(E11).
F
E14
01
Locking/electric
lock
The door leaf got caught in the
locking/electric lock.
Feedback: the electric lock ELFb
does not switch.
Check the function of the locking/
electric lock.
Feedback: check the electric lock ELFb.
When opening from a
closed position.
H
02
The inverted operation has no
locking, or the interlocking force
Fch has not been programmed.
Program/increase the interlocking
force Fch.
At the end of the
teach-in procedure.
W
E15
01
Obstacle in ope
-
ning direction
Too many successive obstacles
have occured.
Examine the installation.
Remove the obstacle.
Move the door leaf to the target
position.
Permanent.
H, A
Restart after 60 s.
02
Obstacle in closing
direction
E16
01
Temperature
Temperature on output level has
reached 81 °C.
Respect the applicaiton limits.
Permanent.
A
Drive unit functions
with reduced power.
02
Temperature on output level has
reached 91 °C.
A
Drive unit has stop
-
ped.
Содержание ETS 64-R
Страница 96: ......
Страница 97: ......
Страница 98: ......
Страница 99: ......
Страница 100: ......
Страница 101: ......
Страница 102: ......
Страница 103: ......
Страница 104: ......
Страница 105: ......
Страница 106: ......
Страница 107: ......
Страница 108: ......
Страница 109: ......
Страница 110: ......
Страница 111: ......
Страница 112: ......