Mounting and operating instructions
5.4
External elements
1. Mount all the required control and safety elements at their respective place.
2. Lead the cables of the elements up to the drive mechanism (by customers).
3. Connect the cables according to the diagram E4-0141-713_ECO (in the appendix).
Note:
If an electric lock is provided, its connection rating is 24 VDC and max. 0,8 A (or
24 VAC/1,5 A by customers). It should be designed for a duty cycle of 100 %. The elec
-
tric lock locks the door leaf in the desired operating modes and is configurable.
Attention:
For the Inverse application it is compulsory to use an electric lock or a holding magnet
which maintains the door leaf in the closed position and must answer the following
requirements:
• tested and homologated for escape and rescue ways
• opening also under preload (load-independent unlocking without jamming)
• 24 VDC / 100 % duty cycle
• opening without mains power (normally open)
The starting delay TDelay must be > 0 s and the relieving force during unlocking FDelay
must be adjusted in accordance.
Electric lock or holding magnet must be connected in reverse order in comparison to
the standard drive mechanism (see wiring diagram E4-0141-713_ECO in the appendix).
Содержание ETS 64-R
Страница 96: ......
Страница 97: ......
Страница 98: ......
Страница 99: ......
Страница 100: ......
Страница 101: ......
Страница 102: ......
Страница 103: ......
Страница 104: ......
Страница 105: ......
Страница 106: ......
Страница 107: ......
Страница 108: ......
Страница 109: ......
Страница 110: ......
Страница 111: ......
Страница 112: ......