Page 47
Model TC80
Relay Hold Time
Read/Write Timed Relay Hold Time (0 - Off, 1 - held
for the duration time, 2 - du 15sec., 3 - duration
+ 30sec., 4 - du 1min., 5 - du 2min., 6 -
du 5 min., 7 - du 15min., 8 - du
30min.)
1
16 bit
Integer
RW
Y
35
23
4-20 mA Channel Number to
read/write
4-20 mA channel number to access data (0 - 1st 4-
20mA, 1 - 2nd 4-20)
1
16 bit
Integer
RW
Y
36
24
4-20 Analog Type
Read/Write 4-20 Type (0 - Range, 1 - Temperature, 2
- Sentinel)
1
16 bit
Integer
RW
Y
37
25
4-20 Analog Range, 4mA
range (hi word)
Read/Write 4mA range (bytes 3 and 2) applies to
both range and temperature types
2
32 bit
Floating
Point
RW
Y
38
26
4-20 Analog Range, 4mA
range (lo word)
Read/Write 4mA range (bytes 1 and 0) applies to
both range and temperature types
39
27
4-20 Analog Range, 20mA
range (hi word)
Read/Write 4mA range (bytes 3 and 2) applies to
both range and temperature types
2
32 bit
Floating
Point
RW
Y
40
28
4-20 Analog Range, 20mA
range (lo word)
Read/Write 4mA range (bytes 1 and 0) applies to
both range and temperature types
41
29
Long Tag Line number to
read/write
Tag Line number to access data (0 - Line 1, 1 - Line 2)
1
16 bit
Integer
RW
Y
42
2A
Long Tag Line 1 (16
characters max)
ASCII character bytes 0 and 1, ex. "AB" A - 65 (41
hexadecimal), B - 66 (42 hex), send 6566 (4142 hex).
The characters permitted are space ' ' (32 base 10, 20
hex) through '}' 125 base 10, 7D hex).
1
16 bit
Integer
RW
Y
43
2B
Long Tag Line
ASCII bytes 2 and 3
1
16 bit
Integer
RW
Y
44
2C
Long Tag Line
ASCII bytes4 and 5
1
16 bit
Integer
RW
Y
45
2D
Long Tag Line
ASCII bytes 6 and 7
1
16 bit
Integer
RW
Y
46
2E
Long Tag Line
ASCII bytes 8 and 9
1
16 bit
Integer
RW
Y
47
2F
Long Tag Line
ASCII bytes 10 and 11
1
16 bit
Integer
RW
Y
48
30
Long Tag Line
ASCII bytes 12 and 13
1
16 bit
Integer
RW
Y
49
31
Long Tag Line
ASCII bytes 14 and 15
1
16 bit
Integer
RW
Y
50
32
Initiate T80 Parameter
Storage
Signals the user has completed entering the data and
wants it stored. Write any value.
1
16 bit
Integer
RW
51
33
Sensor Channel to
read/write
Sensor channel number to access data (0 - Sensor 1,
1 - Sensor 2)
1
16 bit
Integer
RW
52
34
S80 Mode
Unit operating mode (0-
1
16 bit
Integer
R
53
35
S80 Serial Number (hi word)
Unit Serial Number (32 bit integer hi word)
2
32 bit
Long
Integer
R
54
36
S80 Serial Number (lo word)
Unit Serial Number (32 bit integer lo word)
55
37
S80 Fault Status
1
16 bit
Integer
R
56
38
S80 Sensor Type
Specific S80 sensor type (see S80 Sensor Types tab)
1
16 bit
Integer
R
57
39
S80 Sensor Chemical Type
Specific chemicals the S80 is set to detect (see S80
Sensor Types tab)
1
16 bit
Integer
RW
Y
58
3A
S80 Max Range (hi word)
Max sensor range (bytes 3 and 2)
2
32 bit
Floating
Point
R
59
3B
S80 Max Range (lo word)
Max sensor range (bytes 1 and 0)
60
3C
S80 Min Range (hi word)
Min sensor range (bytes 3 and 2)
2
32 bit
Floating
Point
R
61
3D
S80 Min Range (lo word)
Min sensor range (bytes 1 and 0)
62
3E
S80 Sensor Value (hi word)
Current sensor value (bytes 3 and 2)
2
32 bit
Floating
Point
R
63
3F
S80 Sensor Value (lo word)
Current sensor value (bytes 1 and 0)
64
40
S80 Sensor Voltage (hi
word)
Corresponding sensor voltage to the sensor value
(byte 3 and byte 2)
2
32 bit
Floating
Point
R
65
41