24
TEMP
allows the
displayed temperature to be trimmed to agree with actual process temperature.
3.2.3
CONFIG
(C
ONFIGURATION
M
ENU
)
Four options are available in the Configure Menu,
XMTR, SENSOR, LOAD DEFAULT
and
Dampen
.
XMTR
enters the Transmitter Configuration menu.
o
LCD
access
the Display Configuration Menu
SETUP
adjust screen lighting characteristics
Temp.
Choose °C or °F
CONT
adjust Contrast
BACK LIGHT
adjust Backlight Timeout
,
from always
ON to OFF after 10 minutes
GRAPH
provides the choice of which Graph style is displayed
on the Home screen.
LINE ,
Moving average, vertical scale set to 0-100%
of the 4-20 mA output and user defined time scale
GAUGE,
Current reading 0-100% of 4-20 mA range
BAR,
Current reading 0-100% of 4-20 mA range
LABELS
TAG,
Enter up to 2 lines x 16 characters, example,
Name, tag #... Displayed in INFO screen
TAG ON,
Turn TAG ON/OFF, adds TAG to Main
Display Sequence, DATA → mV → GRAF → TAG →
DATA
POP UP
, Turns ON/OFF, the double tap HOME
Screen pop up memo
SENSOR
, Enter up to 2 lines x 16 characters
o
OUTPUT
access the Output Configuration Menu
4-20 mA
configure 4-20 mA output (PV or Temp or More)
PV RANGE
Enter 4 mA value and 20 mA value
Temp RANGE
Enter 4 mA value and 20 mA value
MORE
o
CAL
Trim 4.00 mA and 20.00 mA output
o
FAULT
Choose fault condition 3.5 mA, 22
mA, None
RELAY
RLY1,2,3
Choose relay type:
o
Alarm
, enter the Set point ON, Set Point OFF, Expiration time, Delay ON
and Delay OFF times and the State,
energize
: changes state from de-
energized to energized on alarm.
o
Timed,
Enter Period, Duration times and
Hold On/Off
o
Fault
, No input required, relay condition
changes from energize to de-energize.