CPX200NB ALARM CONTROL UNIT – INSTALLER MANUAL
64 / 116
with the line. This lock will last until disarming. If the input is selected as the
"Alarm after time for exit", then "Interlocking after time for exit" has priority -
the zone will be blocked and will not generate an alarm.
If the line is set to "After time for exit" and is violated or sabotaged after the
time for exit, then is automatically blocked (bypass is activated). User can
unlock the input by use the function 50 # (block inputs).
8.3.1.4.
Sensitivity
That parameter defines a minimum time the change must maintain at the particular
zone, to be detected by a transmitter. Default factory setting of the parameter is
400 ms.
8.3.1.5.
Delay
The parameter is active for delayed and perimeter exit zones only. It defines a time
from the zone disruption was detected after which an alarm is generated.
8.3.1.6.
Alarm after time for exit
When selected, the alarm will be generated if the line remains violated when the time
to exit is up.
When deselected, alarm will NOT be generated in above case.
First alarm will be generated after the line is returned and violated again. .