CPX200NB ALARM CONTROL UNIT – INSTALLER MANUAL
50 / 116
7.3.1.5.2.
Remote connection
As explained above the equipment and software allows full configuration using
GPRS connection or CSD channel. For such programming mode the connection
parameters shall be adequately defined.
GPRS connection
The configuration of that mode requires the activation of File option from Main
Menu, and selecting Connection function (or clicking
icon on a taskbar) and
opening GPRS tab.
The following window will be displayed on the screen.
Define:
Connection name, e.g. Remote
Select analyser name, e.g. primary
Enter analyser name, e.g. www.ebs.pl
Enter the port on which analyser will listen to instructions, e.g. 9000
Click [Add] button to confirm the setting. The connection is saved (and moved to
the table). From that moment the program will enable a remote connection with
the equipment and allows reading and saving the parameters in the equipment’s
memory.
NOTE: Such parameters as analyser’s name, analyser’s
address, port refer to the settings of the OSM.Server
monitoring system receiver. Remote programming is available
only in case the above mentioned equipment (software) is
used.
CSD connection
The configuration of that mode requires activation of File option from Main Menu,
and selecting Connection function (or clicking
icon on a taskbar) and opening
GSM Modem tab.
The window will be displayed on the screen where you define: