9 Register interface
9.2 Register description and register access
94
XI/ON: XNE-2CNT-2PWM
04/2011 MN05002035Z-EN
www.eaton.com
Register CNT2
REG_CNT2_CNT
0×40
Actual binary value of the CNT2
-
V
WR
RD
REG_CNT2_MV
0×41
Measured value CNT2
32 bit unsigned
V
RD
...
0×42
reserved
-
-
-
REG_CNT2_LOADVAL
0×43
Load value CNT2
32 bit signed
0×00 00 00 00
NV
WR
RD
REG_CNT2_LOLIMIT
0×44
lower count limit CNT2
0×080 00 00 00 NV
WR
RD
REG_CNT2_HILIMIT
0×45
Upper count limit CNT2
0×7F FF FF FF
NV
WR
RD
REG_CNT2_CMP0
0×46
Compare value 0 CNT2
0×00 00 00 00
NV
WR
RD
REG_CNT2_CMP1
0×47
Compare value 1 CNT2
0×00 00 00 00
NV
WR
RD
REG_CNT2_LATCH
0×48
Buffer
-
V
RD
REG_CNT2_INTTIME
0×49
Integration time CNT2
in 10 ms/bit
32 bit unsigned 0×00 00 00 0A
(100 ms)
NV
WR
RD
REG_CNT2_MUL
0×4A
Factor CNT2
0×00 00 00 01
NV
WR
RD
REG_CNT2_DIV
0×4B
Divisor CNT2
0×00 00 00 01
NV
WR
RD
REG_CNT2_IPI
0×4C
Pulses per integration time
-
V
RD
REG_CNT2_TO
0×4D
Time out CNT2 in 10 ms/bit
0×00 00 00 00
NV
WR
RD
REG_CNT2_LOGMSG
0×4E
Buffer of the MSG register at
MSGLOG
-
V
RD
REG_CNT2_DO1_HYS
0×4F
Hysteresis of the D2 and
STS_DBP2 for CNT2
0×00 00 00 0A
(10 pulses)
NV
WR
RD
REG_CNT2_DO2_IMP
0×40
Pulse time for a pulse output at
D2 in 10 ms/bit
32 bit unsigned 0×00 00 00 0A
(100 ms)
NV
WR
RD
0×51
to
0× 5F
reserved
Designation
No.
Description
Format
Default (HEX)
Storag
e
in mo
dule
Process output
Process inp
u
t
Paramete
rs
Diagnostics
V = volatile
NV = non-volatile
RD = read access
WR = write access