11 Representation of the XNE-2CNT-2PWM in CANopen
11.1 Objects for counter modules
XI/ON: XNE-2CNT-2PWM
04/2011 MN05002035Z-EN
www.eaton.com
145
Object 6C01hex – Work Area Low Limit
The object 6C01
hex
defines the value for the lower count limit (
→
In the event of an underflow, bit 2 in Object 6C00hex – Area State Register (page 144) and bit
6 in Object 5803hex – Encoder Flags (page 112) are set.
The object corresponds to object 6401
hex
in accordance with CiA DS-406.
Structure of the data bytes
Table 58:
Object 6C01
hex
Feature
Sub-index
Description
Name
Work Area Low Limit
Object code
ARRAY
PDO mapping
-
Data type
0×00
Unsigned 8
0×01
to 0×47
Unsigned 32
Access
0×00
ro
0×01
to 0×47
rw
Default value
0×00
-
0×01
to 0×47
-
Sub-index
0×00
≤
n
≥
0×47
Byte
Description
Register
Register no.
n
= CNT1
0 to 3
lower count limit of CNT1
(Register interface (page 91))
0×24
n + 1
= CNT2
0 to 3
lower count limit of CNT2
(Register interface (page 91))
0×44
Note
If the count limits are loaded with (REG_CNTx_HILIMIT)
≤
(REG_CNTx_LOLIMIT),
the value is transferred and an error message is recorded in the REG_CONFIG_
ERRSTS (CNTx) (page 81).
If a count limit is set so that the actual count value is outside the count range, the
current value is set to the count limit which is closest to it. In this case
no
error mes-
sage is recorded in register REG_CONFIG_ERRSTS.