4 Functions of the count inputs (CNT1 and CNT2)
4.1 Basic functions of the count inputs CNTx
36
XI/ON: XNE-2CNT-2PWM
04/2011 MN05002035Z-EN
www.eaton.com
4.1.3
Set count limits
The count limits are contained in the following registers:
The count limits can be set via the Process output / control interface (page 32).
Register name
Register no.
Max. value
Min. value
Default value
REG_CNT1_LOLIMIT
lower count limit CNT1
36
(0×24)
+2147483647
(0×7F FF FF FF)
-2147483648
(0×80 00 00 00)
-2147483648
(0×80 00 00 00)
REG_CNT1_HILIMIT
upper count limit CNT1
37
(0×25)
+2147483647
(0×7F FF FF FF)
REG_CNT2_LOLIMIT
lower count limit CNT2
68
(0×44)
+2147483647
(0×7F FF FF FF)
REG_CNT2_HILIMIT
upper count limit CNT2
69
(0×45)
-2147483648
(0×80 00 00 00)
Note
If the count limits are loaded with (REG_CNTx_HILIMIT)
≤
(REG_CNTx_LOLIMIT),
the value is transferred and an error message is recorded in the
REG_CONFIG_ ERRSTS (CNTx) (page 81).
If a count limit is set so that the actual count value is outside the count range, the
current value is set to the count limit which is closest to it. In this case
no
error mes-
sage is recorded in register REG_CONFIG_ERRSTS.