4 Functions of the count inputs (CNT1 and CNT2)
4.1 Basic functions of the count inputs CNTx
XI/ON: XNE-2CNT-2PWM
04/2011 MN05002035Z-EN
www.eaton.com
41
1
1
Down
Load value
The counting operation starts with the current count value.
Upper
count limit
If, while counting upwards, the counter reaches the upper count limit and
another counting pulse is received, the counter value jumps to the lower count
limit. The counter continues counting starting at the lower count limit.
Lower
count limit
If, while counting downwards, the counter reaches the lower count limit and
another counting pulse is received, the counter value jumps to the load value.
The counter continues counting starting at the load value.
Internal enable
The internal enable is not automatically reset. The counter remains active.
Note
The counting operation starts with the current count value. The user can preset this
value to a defined value (
→
see Load load value (page 35)).
Table 10:
Main count
direction with
CNTx_SINGLE
=
0
Main count direction CNTx
Bit 1
Bit 0