4 Functions of the count inputs (CNT1 and CNT2)
4.1 Basic functions of the count inputs CNTx
XI/ON: XNE-2CNT-2PWM
04/2011 MN05002035Z-EN
www.eaton.com
35
4
Functions of the count inputs (CNT1 and CNT2)
4.1
Basic functions of the count inputs CNTx
4.1.1
Load count value
The count value can be loaded directly via the Register interface (page 91). To do so, the
register (REG_CNTx_CNT) has to be written directly with the desired count value using the
access via the Process output / control interface (page 32).
4.1.2
Load load value
The load value is loaded via the Process output / control interface (page 32) and copied into
the count value (REG_CNTx_CNT) due to certain events.
These events have to be defined via the Parameter data of the module (page 25).
Register name
Register no.
Max. value
Min. value
Default value
32
(0×20)
+2147483647
(0×7F FF FF FF)
-2147483648
(0×80 00 00 00)
0
(0×00 00 00 00)
64
(0×40)
Note
If the value to be loaded is outside the count limits, the value is not transferred as
count value, but the count limit which is the closest to the value is loaded instead.
No error message is set in REG_CONFIG_ ERRSTS (CNTx) (page 81).
Register name
Register no.
Max. value
Min. value
Default value
35
(0×23)
+2147483647
(0×7F FF FF FF)
-2147483648
(0×80 00 00 00)
0
(0×00 00 00 00)
67
(0×43)
Note
If a load value is loaded which is outside the count limits, the value is transferred and
an error message is generated in REG_CONFIG_ ERRSTS (CNTx) (page 81).