4 Integration of the module in DeviceNet
4.1 SWIRE module class (VSC121)
38
XI/ON: XNE-1SWIRE
09/2011 MN05002016Z-EN
www.eaton.com
Attr.No.
dec.
(hex.)
Attribute name
Access
Type
Description
100
(64
hex
)
MAX OBJECT ATTRIBUTE G
USINT
Contains the number of the last implemented
object attribute.
101
(65
hex
)
MODULE PRESENT
G
BOOL
0: XI/ON module is not fitted, empty base module.
1: XI/ON module is fitted.
102
(66
hex
)
TERMINAL SLOT NUMBER G
USINT
The slot number of the base module belonging to
the module (base module on the right of the
gateway = No. 1). Corresponds to the relevant
instance number within the TERMINAL SLOT
CLASS (description in AWB2700-1405).
103
(67
hex
)
MODULE ID
G
DWORD Contains the module ID.
104
(68
hex
)
MODULE ORDER NUMBERG
UDINT
Contains the order number of the module.
105
(69
hex
)
MODULE ORDER NAME
G
SHORT_
STRING
Contains the module name, e.g. “XN-1RS485/422”.
106
(6A
hex
)
MODULE REVISION
NUMBER
G
USINT
Contains the revision number of the module firm-
ware.
107
(6B
hex
)
MODULE TYPE ID
G
ENUM
USINT
Provides information on the module type:
0 (00
hex
) unknown module type
1 (01
hex
) digital I/O module
17 (11
hex
) analog module I/O voltage
18 (12
hex
) analog module I/O current
19 (13
hex
) analog module PT temperature
20 (14
hex
) analog module thermo temperature
31 (1F
hex
) analog module current/voltage
33 (21
hex
) 16-bit counter module
34 (22
hex
) 32-bit counter module
40 (28
hex
) SSI module
49 (31
hex
) motor starter module as DOL or reversing
starter
50 (32
hex
) electronic motor starter
65 (41
hex
) RS232 module
66 (42
hex
) RS485/422 module
67 (43
hex
) TTY module
108
(6C
hex
)
MODULE COMMAND
INTERFACE
G/S
ARRAY Command interface of the XI/ON module
ARRAY OF:
BYTE: Command byte sequence
109
(6D
hex
)
MODULE RESPONSE
INTERFACE
G
ARRAY Signal interface of the XI/ON module
ARRAY OF:
BYTE: Signal byte sequence
110
(6E
hex
)
MODULE REGISTERED
INDEX
G
ENUM
USINT
Contains the index number listed in all module lists.
111
(6F
hex
)
NUMBER OF SUPPORTED
INPUT CHANNELS
G
USINT
Shows the number of input channels supported by
this module instance.