7.2
Configuration of the XNE-1SWIRE as local module
on the XN-PLC-CANopen
After the XN-PLC-CANopen and XN-GWBR-CANopen have been configured, the
modules located in the station must be parameterized for the required function.
In this example the XNE-1SWIRE is set for the following functions:
•
The physical structure of the SWIRE bus should be stored automatically in the
XNE-1SWIRE. This deactivates the function of the CFG button of the XNE-
1SWIRE.
• Activate automatic SWIRE configuration.
•
The PLC should only exchange data with the SWIRE bus if all 8 of the SWIRE-
DIL modules configured in the PLC (SET configuration) are present in the SWIRE
configuration stored in the XNE-1SWIRE.
• Activate PLC configuration check.
• Set configuration check to Bus-oriented.
•
PKZ trips should not generate any error messages as the information is evalu-
ated in the input image.
• Deactivate group error -PKZ error-.
• Deactivate field -PKZ error-.
Fig. 16 Parameterization of module properties
The following takes place after the program is loaded and started on the XN-PLC-
CANopen:
•
The XNE-1SWIRE automatically starts the operation of the SWIRE bus fitted
with 8 slaves (SW LED lit)
•
The XNE-1SWIRE exchanges data with the PLC if the subsequent PLC configu-
ration check finds that the configuration stored in the XNE-1SWIRE completely
matches the SET configuration stored in the PLC (RDY LED lit).