3 Integration of the module in PROFIBUS-DP
3.1 Data mapping under PROFIBUS-DP
32
XI/ON: XNE-1SWIRE
09/2011 MN05002016Z-EN
www.eaton.com
Tab. 14 Meaning of diagnostics data bits
Byte 3,4
TYPE
ERR
Sx
Device configuration, slave x
Info field for the individual indication of a configuration
error as error message. If the TYPE
INFO
parameter is
set with individual diagnostics, the error is indicated in
this bit field as soon as a PLC configuration check
detects differing slave numbers, types or position of an
SWIRE slave.
0
OK
No error is present and the slave is in
data exchange mode or diagnostics
function has been deactivated via the
parameter setting.
1
Incorrect
No error is present and the slave is
not
in data exchange mode.
Byte 5,6
SD
ERR
Sx
Communication, slave x
Info field for the individual indication of slave offline or
slave diagnostics as error message. The fault is indi-
cated in this bit field if the parameter setting SD
INFO
is
set with individual diagnostics.
0
OK
No error is present or diagnostics func-
tion has been deactivated via the
parameter setting.
1
Offline
The slave has set its diagnostics bit or
the slave was in data exchange with
the SWIRE master but is not any
longer.
Byte 7,8
PKZ
ERR
Sx
Only SWIRE-DIL: Overcurrent protective circuit-
breaker slave x
Info field for the individual indication of the tripping a
motor-protective circuit-breaker (PKZ) as error
message. If the PKZ
INFO
is set for single diagnostics,
this bit field indicates the error as soon as the PKZ of
the slave Sx has tripped.
0
OK
The PKZ of the slave has not tripped or
diagnostics function has been deacti-
vated via the parameter setting.
1
Tripped
The PKZ of the slave has tripped.
Byte
Designation
Status
Comment