11. Commissioning
6. Go to option ‘
Accept
’ at the end of the list. Re-confirm the system configuration.
7. Outstations are now addressed. Outstations would now be able to communicate
with panel.
8. An error message will be displayed if auto learn process is not successful due to
any failure – eg: No OS connected, Loop break etc.
9. Correct the condition and perform the learn until successful.
trouBLESHootInG:
If any of the wiring is not correct, the number of outstations
detected will be incorrect. Fault Log / Learn status can be referred to identify the
problem. After fixing the issue, perform the Outstation learn process again.
ote:
n
Outstation Learn process must be performed whenever an Outstation has
been added, removed or replaced in an existing system or details are changed
for any Outstation. The system will prompt the installer to keep the names
and locations of all existing outstations, or overwrite / delete them.
ote:
n
Two options are added as sub menu under ‘
Install
’ once learn is successful -
Webserver, Config. Backup / Restore.
4 Outstations Found
Accept
04: Type B
V1.01
SN: 1359847873
4 Outstations Found
Accept
04: Type B
V1.01
SN: 1359847873
Outstation Learn OK