10. Installation
10.3 Network topology - Standalone
VoCALL 16 has been designed to enable simple installation and aid ease of expansion
of an installed system. The MX16 main panel can be connected to Outstation variants –
Type A, Type B on a single loop. Up to 16 Outstations, in any combination, can be
connected to the Panel. Each Outstation on the loop is automatically soft addressed
by the panel.
distance:
Maximum distance between Panel and Outstation – 200m
Maximum distance between two Outstations – 200m
Maximum loop length - Outstation: 2 Km
Figure 27. topology - Standalone
OS 1
OS 2
OS 15
OS 16
MX16
FP200, 200m