24
Operation
EATON TFX INSTALLATION AND OPERATION MANUAL
6046279-001
September 2019
www.eaton.com
STANDARD CHANNEL
8. Select the
s
tanDarD
C
hannel
tab.
9. Set and save the following:
Table 18: Communication settings in PGN 61444 –
Standard Channel
Description
Selection Function
f
ull
Can
m
essage
o
BjeCt
Set
Assigns the receive message to a
controller channel.
ID-
l
ength
29-bit ID
ID length of the CAN message
to be received.
D
own
-s
ample
Set
Receive message max. every 100 ms.
C
oB
-ID
Fix
(00F00400)
Fixed identifier of the receive message
(J1939 PGN 61444).
m
ask
Fix
(00FFFF00)
Determines that bits 8 … 24 of the
identifier fixed in C
oB
-ID must not vary
in the identifier of the received message.
In the J1939 protocol, the first bits of the
identifier define the priority and the last
bits of the identifier define the source
address. These are ignored when the
message is received.
5.2.3.2 Example 1: Log all data bytes every 60 seconds
In this example, all data bytes are simply logged cyclically
every 60 seconds. There are no additional conditions, and
the data bytes are not checked.
LOGGING - CONDITIONS
Make the following settings for the PGN 61444 object.
1. Select the
l
ogging
tab.
2. Select the
C
onDitions
tab.
3. Set and save the following:
Table 19: Logging in PGN 61444 - Conditions
Description
Selection
Function
l
ogging
e
naBleD
Set
Logging enabled
l
og
m
essage
on
AND
The data is only logged when timeout is
reached AND the condition is met.
l
ogging
perioD
Use a fixed
value (60000)
Duration of the logging interval
in milliseconds.
C
onDition
/
a
lways
true
Set
Logging takes place without prior
checking of conditions.
PAYLOAD
4. Select the
p
ayloaD
tab.
5. Set and save the following:
Table 20: Logging in PGN 61444 - Payload
Description
Selection
Function
l
og
r
eCeiveD
Can m
essage
Set
Log data of the receive CAN message.
B
ytes
to
log
All
Log all data bytes.
Содержание TFX CAN link mobile 3311 Variant
Страница 1: ...TFX Installation and Operation Manual ...