![Eaton Scantronic i-on10 Скачать руководство пользователя страница 52](http://html1.mh-extra.com/html/eaton/scantronic-i-on10/scantronic-i-on10_configuration-manual_3911046052.webp)
System Options Menu
Page 52
Installer Timeout
The installer is automatically logged out of the Installer menu if there is no activity after the
specified period.
Service Date
This option allows you to specify the date when the next maintenance service of the
system is due. If
Service Banner
is enabled, the message "SERVICE REQUIRED" is
displayed at keypads up to four hours after the start of the
Service Date
.
Service Banner
Enabling this option allows the "SERVICE REQUIRED" message to be displayed at
keypads on the date specified by
Service Date
.
Confirmation
The options in the
Confirmation
menu depend on the
Confirmation Mode
you select.
Confirmation Mode
The options in
Confirmation Mode
depend on the country selected during the initial power
up (see page 19):
If the country is anywhere other than the UK, Basic confirmation mode is always
used.
If the country is the UK,
Confirmation Mode
contains three options:
Basic
,
DD243
and
BS8243
.
The setting for
Confirmation Mode
determines the events the control unit requires to create
a "confirmed alarm":
Basic (default and only setting if the country is not the UK)
– A confirmed alarm is
generated when a second zone alarm is activated while the system is in an alarm
state.
BS8243 or DD243 (if the country is the UK)
– A confirmed alarm is generated when
a second zone alarm is triggered within the period of the confirmation timer setting
(
Confirmation Time
or
HUA Confirm Time
, as applicable). If you select either of
these options, additional options are displayed to define the meaning of a confirmed
alarm.
If the first ("unconfirmed") alarm is caused by the expiry of the entry timer, then for:
DD243
– A further two zones that are not on the entry route must be triggered to
generate a Burg Confirmed Alarm.
BS8243
– One zone not on the entry route must be triggered to generate a Burg
Confirmed Alarm.