Introduction
6
Powerware
®
Prestige Series Installation and Operator’s Manual for IBM Applications (650 VA - 1500 VA)
Uncontrolled Copy
Prestige with Additional Battery Cabinets
Load
(VA)
Load
Battery Cabinet Configurations for EXT Models
(Approximate Battery Time in Minutes)
(VA)
at
*
Load
(W)
120V EXT Models
.7 PF*
( )
1 Cabinet
2 Cabinets
3 Cabinets
4 Cabinets
200
140
240
404
570
737
400
280
128
220
311
402
600
420
81
152
215
277
800
560
57
110
162
210
1000
700
43
83
127
168
1250
875
33
62
95
131
1500
1050
25
48
74
101
208V-240V EXT Models
200
140
203
346
491
637
400
280
117
201
285
371
600
420
76
141
200
260
800
560
55
105
153
199
1000
700
42
81
124
161
1250
875
32
61
94
129
1500
1050
25
49
74
102
*
Typical Power Factor (PF)
NOTE
The EXT Models have “P2” in the rating label model number.