Installation
48
Powerware
®
Prestige Series Installation and Operator’s Manual for IBM Applications (650 VA - 1500 VA)
Uncontrolled Copy
8.
Press and hold the Output On button until the alarm beeps to
select and save the output voltage. Failure to release the button
immediately after the beep will cause the UPS to abort the
setup.
NOTE
If you do not save a selection within two minutes, the setup automatically
aborts and switches back to the original configuration.
9.
Turn on the equipment that is connected to the UPS.
10.
Press and hold the Output On button until you hear the UPS
beep (approximately one second).
The
indicator remains lit and the Self Test indicator turns
on. The front panel displays the percentage of full load being
applied to the UPS. The UPS is now in Normal mode with the
load online. See “Normal Mode” on page 50 for more
information.
11.
The installation is complete. Continue to Chapter 4, “UPS
Operation” on page 49 for more information on the UPS.
Troubleshooting Tips
If you should encounter any problems during startup, see the
troubleshooting chart on page 73.
The UPS is shipped with the battery(s) charged. However, batteries may
lose some of the charge during shipping and storage. You can use the
UPS immediately after unpacking, but it may not provide the full-rated
backup time during a power failure. Upon initial startup, the UPS may
need to operate for approximately 8 hours before the battery is fully
charged and full battery-backup time is available. If the Battery Fault
indicator flashes, operate the UPS for 24 hours to fully charge the
battery.