4.4 Electrically connecting the cabinet sections
1.
Unfasten the front door latch and swing the door open (see Figure 4-1 on page 33).
2.
Remove the retaining screw located inside the door at the bottom hinge pivot point, then lift the
door off. Retain the hardware for later use.
3.
Remove the screws securing the ISBM section right bottom protective cover panel and remove the
panel to gain access to the internal input, output, and battery terminals. Retain the hardware for
later use.
NOTE
AC and DC input intercabinet power wiring harnesses are supplied coiled and secured in the
UPM wireway on the left side of the UPM section (see Figure 4-3 on page 34).
4.
Locate the AC and DC input intercabinet power wiring harnesses (long cables labeled Ex/UPM1,
Ex/UPM2, Ex/UPM3, CB1-2/UPMx, CB1-4/UPMx, CB1-6/UPMx). Remove wire ties as necessary
and uncoil the cables.
5.
Locate the CB1-2/UPMx, CB1-4/UPMx, CB1-6/UPMx power wiring harnesses. Route these
harnesses through the wiring access in the right side panel of the ISBM section to the AC Input to
UPMs terminals. See Figure 4-7 on page 41 for terminal locations.
NOTE
Two cable lugs will be connected to each terminal stud. When connecting the cable lugs, install
the first lug on the stud with the raised barrel portion facing the back of the cabinet. Install the
second lug with the raised barrel portion facing the front of the cabinet.
6.
Locate the intercabinet wiring terminal hardware kit packed on the bottom right side of the ISBM
section.
7.
Using hardware from the intercabinet wiring terminal hardware kit, connect phase L1, L2, and L3
cable lug connections to the AC input to UPMs terminals. Follow the callout details in Figure 4-8 on
page 42 to connect the correct cable lug to the proper terminals.
8.
Locate the E4/UPMx and E5/UPMx power wiring harnesses. Route these harnesses through the
wiring access in the right side panel of the ISBM section to the DC input to UPMs terminals. See
Figure 4-7 for terminal locations.
NOTE
Two cable lugs will be connected to each terminal stud. When connecting the cable lugs, install
the first lug on the stud with the raised barrel portion facing the back of the cabinet. Install the
second lug with the raised barrel portion facing the front of the cabinet.
9.
Using hardware from the intercabinet wiring terminal hardware kit, connect the positive and
negative cable lug connections to the DC input to ISBM terminals. Follow the callout details in
Figure 4-9 on page 42 to connect the correct cable lug to the proper terminals.