UPS 675-1100 kVA 3..4x(225-275) kVA
1029052
User’s and Installation Guide
Revision 008
3.
Press the CONTROLS pushbutton on the System Status menu bar. The Bypass Control Command
screen is displayed.
4.
On the Bypass Control Command screen, select
GO TO BYPASS
.
5.
Press the SELECT pushbutton on the Bypass Command menu bar.
All of the UPSs transfer to Bypass mode and the critical load is immediately supplied by the bypass
source. If the bypass source is not available, the power module remains on and an alarm sounds.
The BYPASS status indicator is illuminated. The Bypass status indicates
ON
. The UPM status indi-
cates
READY
. The power module remains on.
WARNING
Power is present inside the UPS cabinet.
7.4.12 Transfer from Bypass to Normal mode
To transfer the critical load to Normal mode:
1.
If not already closed, close the battery breaker.
2.
On any UPS, press the CONTROLS pushbutton on the main menu bar. The System Status screen
is displayed.
3.
On the System Status screen, select the
UPS
command.
4.
Press the CONTROLS pushbutton on the System Status menu bar. The UPS Control Command
screen is displayed.
5.
On the UPS Control Command screen, select
GO ONLINE
.
6.
Press the SELECT pushbutton on the UPS Command menu bar.
All of the UPSs transfer to Normal mode. If the power module is not available, the system remains
on bypass and an alarm sounds.
The NORMAL status indicator is illuminated. The UPS status indicates
ONLINE
.
The UPM status indicates
ONLINE
.
7.4.13 Transfer from Normal to Energy Saver System
To transfer the critical load to Energy Saver System:
NOTE
The Energy Saver System commands are displayed only if enabled at the factory or by an Eaton
Customer Service Engineer.
1.
On any UPS, press the CONTROLS pushbutton on the main menu bar. The System Status screen
is displayed.
2.
On the System Status screen, select the
UPS
command.
3.
Press the CONTROLS pushbutton on the System Status menu bar. The UPS Control Command
screen is displayed.
4.
On the UPS Control Command screen, select
ENABLE ENERGY SAVER
.
5.
Press the SELECT pushbutton on the UPS Command menu bar.
All of the UPSs transfer to Energy Saver System and the critical load is immediately supplied by the
bypass source. If the bypass source is not available, the power module remains on and an alarm
sounds.
The NORMAL status indicator is illuminated. The UPS status indicates
ENERGY SAVER
. The
Bypass status indicates
ON
. The UPM status indicates
ONLINE
.