UPS 675-1100 kVA 3..4x(225-275) kVA
1029052
User’s and Installation Guide
Revision 008
7.4.16 Transfer from High Alert to Normal mode
To transfer the critical load to Normal mode:
NOTE
The High Alert mode commands are displayed only if enabled at the factory or by an Eaton
Customer Service Engineer.
1.
On any UPS, press the CONTROLS pushbutton on the main menu bar. The System Status screen
is displayed.
2.
On the System Status screen, select the
UPS
command.
3.
Press the CONTROLS pushbutton on the System Status menu bar. The UPS Control Command
screen is displayed.
4.
On the UPS Control Command screen, select
GO ONLINE
.
5.
Press the SELECT pushbutton on the UPS Command menu bar.
All of the UPSs transfer to Normal mode. The NORMAL status indicator is illuminated. The UPS
status indicates
ONLINE
. The UPM status indicates
ONLINE
.
7.4.17 Transfer from Bypass to Energy Saver System
To transfer the critical load to Energy Saver System:
NOTE
The Energy Saver mode commands are displayed only if enabled at the factory or by an Eaton
Customer Service Engineer.
1.
On any UPS, press the CONTROLS pushbutton on the main menu bar. The System Status screen
is displayed.
2.
On the System Status screen, select the
BYPASS
command.
3.
Press the CONTROLS pushbutton on the System Status menu bar. The Bypass Control Command
screen is displayed.
4.
On the Bypass Control Command screen, select
ENABLE ENERGY SAVER
.
5.
Press the SELECT pushbutton on the Bypass Command menu bar.
All of the UPSs transfer to Normal mode and then to Energy Saver System. The critical load is sup-
plied by the bypass source.
The NORMAL status indicator is illuminated. The UPS status indicates
ENERGY SAVER
. The
Bypass status indicates
ON
. The UPM status indicates
ONLINE
. If the battery is not charging, the
power module is off.
7.4.18 Transfer from Energy Saver System to Bypass mode
To transfer the critical load to Bypass mode:
NOTE
The Energy Saver System commands are displayed only if enabled at the factory by an Eaton
Customer Service Engineer.