![Eaton Powerware 9395 Скачать руководство пользователя страница 127](http://html.mh-extra.com/html/eaton/powerware-9395/powerware-9395_user-and-installation-manual_525182127.webp)
1029052
UPS 675-1100 kVA 3..4x(225-275) kVA
119
Revision 008
User’s and Installation Guide
1.
Unfasten the front door latches and swing the doors open on all of the UPSs (see Figure 4-2 on
page 33).
2.
If the UPSs contain input breakers (CB1), verify that all input breakers are open.
3.
Close all MOBs.
4.
Close all UPS input feeder circuit breakers.
5.
If the UPSs contain input breakers (CB1), close all input breakers.
6.
Close all UPS Bypass input feeder circuit breakers.
7.
Close the doors and secure the latches.
8.
Observe the UPS control panel displays becoming active, indicating logic power.
9.
On any UPS, press the CONTROLS pushbutton on the main menu bar. The System Status screen
is displayed.
10. On the System Status screen, verify that the status of the UPS and UPM is
SHUTDOWN
.
11. On the System Status screen, select the
BYPASS
command.
12. Press the CONTROLS pushbutton on the System Status menu bar. The Bypass Control Command
screen is displayed.
13. On the Bypass Control Command screen, select
GO TO BYPASS
.
14. Press the SELECT pushbutton on the Bypass Command menu bar.
The critical load is immediately supplied by the bypass source in Bypass mode from all UPSs.
The BYPASS status indicator is illuminated. The Bypass status indicates
ON
. The UPM status indi-
cates
SHUTDOWN, CLOSE BATTERY
.
7.4.3 Enable Variable Module Management System mode from the UPS
command menu
For instructions, see Section 7.3.5 “Enable Variable Module Management System mode from the UPS
command menu” on page 106.
7.4.4 Disable Variable Module Management System mode from the UPS
command menu
For instructions, see Section 7.3.6 “Disable Variable Module Management System mode from the UPS
command menu” on page 107.
7.4.5 Start Variable Module Management System High Alert mode from
the UPS command menu
For instructions, see Section 7.3.7 “Start Variable Module Management System High Alert mode from
the UPS command menu” on page 107.
7.4.6 Enable Variable Module Management System mode from the bypass
command menu
For instructions, see Section 7.3.8 “Enable Variable Module Management System mode from the
bypass command menu” on page 108.
7.4.7 Disable Variable Module Management System Mode from the
bypass command menu
For instructions, see Section 7.3.9 “Disable Variable Module Management System mode from the
bypass command menu” on page 108.