114
UPS 675-1100 kVA 3..4x(225-275) kVA
1029052
User’s and Installation Guide
Revision 008
5.
Press the SELECT pushbutton on the UPS Command menu bar.
The UPS transfers to Battery mode and then to High Alert mode. After one hour the UPS transfers
to Energy Saver System and the critical load is immediately supplied by the bypass source. If the
bypass source is not available, the power module remains on and an alarm sounds.
The NORMAL status indicator is illuminated. The UPS status indicates
HIGH ALERT
. The UPM sta-
tus indicates
ONLINE
. The power module is on.
7.3.22 Transfer from High Alert to Energy Saver System
To transfer the critical load to Energy Saver System:
NOTE
The High Alert and Energy Saver System commands are displayed only if enabled at the factory
or by an Eaton Customer Service Engineer.
1.
Press the CONTROLS pushbutton on the main menu bar. The System Status screen is displayed.
2.
On the System Status screen, select the
UPS
command.
3.
Press the CONTROLS pushbutton on the System Status menu bar. The UPS Control Command
screen is displayed.
4.
On the UPS Control Command screen, select
ENABLE ENERGY SAVER
.
5.
Press the SELECT pushbutton on the UPS Command menu bar.
The UPS transfers to Energy Saver System and the critical load is immediately supplied by the
bypass source. If the bypass source is not available, the power module remains on and an alarm
sounds.
The NORMAL status indicator is illuminated. The UPS status indicates
ENERGY SAVER
. The
Bypass status indicates
ON
. The UPM status indicates
ONLINE
. If the battery is not charging, the
power module is off.
7.3.23 Transfer from Normal to Bypass mode and shut down UPS
To transfer the critical load to Bypass mode and shut down the UPS, perform the following procedure:
1.
Transfer the critical load to bypass by performing the procedure in Section 7.3.11.
2.
Press the CONTROLS pushbutton on the main menu bar. The System Status screen appears.
3.
Press the pushbutton to display System Controls Screen 2.
4.
Press the UPM OFF pushbutton on the System Controls menu bar.
The UPM status indicates
SHUTDOWN
. The input and output contactors open, the battery breaker or
disconnect is tripped, and the power module is turned off. The bypass source supplies the critical load.
WARNING
Power is present inside the UPS cabinets.
7.3.24 Single UPM shutdown
To shutdown a single UPM:
1.
Press the CONTROLS pushbutton on the main menu bar. The System Status screen is displayed.