![Eaton Powerware 9395 Скачать руководство пользователя страница 142](http://html.mh-extra.com/html/eaton/powerware-9395/powerware-9395_user-and-installation-manual_525182142.webp)
134
UPS 675-1100 kVA 3..4x(225-275) kVA
1029052
User’s and Installation Guide
Revision 008
NOTE
The following instructions are for the Eaton-supplied REPO switch. If a customer-supplied REPO
switch is used, it may not activate in the same manner; refer to the operating instructions
provided with the switch.
To use the REPO switch:
1.
Firmly push the red pushbutton until it locks into place. The switch latches into the activated state.
The input, output, and bypass backfeed contactors open, the battery breaker or disconnect is
tripped, and the power module is turned off immediately, without asking for verification on all
UPSs.
CAUTION
Do not attempt to restart the system after the REPO until the cause of the shutdown has been
identified and cleared.
2.
To deactivate the REPO switch in preparation for restarting the UPS, insert the supplied key and
rotate clockwise until the red pushbutton releases. To remove the key, rotate the key back to the
vertical position.
3.
Restart the UPSs by following the procedure in Section 7.4.1 or Section 7.4.2 on page 118.
WARNING
Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is