![Eaton Powerware 9395 Скачать руководство пользователя страница 131](http://html.mh-extra.com/html/eaton/powerware-9395/powerware-9395_user-and-installation-manual_525182131.webp)
1029052
UPS 675-1100 kVA 3..4x(225-275) kVA
123
Revision 008
User’s and Installation Guide
7.4.14 Transfer from Energy Saver System to Normal mode
To transfer the critical load to Normal mode:
NOTE
The Energy Saver System commands are displayed only if enabled at the factory or by an Eaton
Customer Service Engineer.
1.
On any UPS, press the CONTROLS pushbutton on the main menu bar. The System Status screen
is displayed.
2.
On the System Status screen, select the
UPS
command.
3.
Press the CONTROLS pushbutton on the System Status menu bar. The UPS Control Command
screen is displayed.
4.
On the UPS Control Command screen, select
GO ONLINE
.
5.
Press the SELECT pushbutton on the UPS Command menu bar.
All of the UPSs transfer to Battery mode and then to Normal mode. If the power module is not
available, the system remains on bypass and an alarm sounds.
The NORMAL status indicator is illuminated. The UPS status indicates
ONLINE
. The UPM status
indicates
ONLINE
.
7.4.15 Transfer from Normal to High Alert mode
To transfer the critical load to High Alert mode:
NOTE
The High Alert mode commands are displayed only if enabled at the factory or by an Eaton
Customer Service Engineer.
1.
On any UPS, press the CONTROLS pushbutton on the main menu bar. The System Status screen
is displayed.
2.
On the System Status screen, select the
UPS
command.
3.
Press the CONTROLS pushbutton on the System Status menu bar. The UPS Control Command
screen is displayed.
4.
On the UPS Control Command screen, select
START HIGH ALERT
.
5.
Press the SELECT pushbutton on the UPS Command menu bar.
All of the UPSs transfer to High Alert mode, but remain online. After one hour the UPSs transfer to
Energy Saver System and the critical load is immediately supplied by the bypass source. If the
bypass source is not available, the power module remains on and an alarm sounds.
The NORMAL status indicator is illuminated. The UPS status indicates
HIGH ALERT
. The UPM sta-
tus indicates
ONLINE
. The power module is on.