136
UPS 675-1100 kVA 3..4x(225-275) kVA
1029052
User’s and Installation Guide
Revision 008
LanSafe software uses an RS-232 serial link to communicate with the UPS. The software provides up-
to-date graphics of UPS power and system data and power flow, a complete record of critical power
events, and notification of important UPS or power information. With custom views for monitoring
status and metering information, various user groups can select the most useful view for their specific
needs. LanSafe Power Management Software
8.3 Terminal mode
Terminal mode is supported by all RS-232 serial communication ports of the UPS. The following
settings should be used:
•
Baud rate:19200
•
8 data bits
•
no parity
•
1 stop bit
NOTE
The brackets ([ ]) in the following bullets indicate standard keyboard characters. To use a key
combination, hold down the Escape key and press the indicated letter key.
In Terminal mode, the user can request the following:
•
[ESC] [A] displays the Active Alarms.
•
[ESC] [H] displays the Event History.
•
[ESC] [N] displays the Node Bits Setup.
•
[ESC] [V] displays the UPS control panel.
•
[ESC] [Q] Quit.
8.3.1 Display UPS control panel
When this function is invoked, a facsimile of the UPS control panel is displayed on the terminal screen.
All controls are functional and can control the UPS remotely. The only exception is the Load Off control
which requires the operator to press and hold the local control for three seconds to shut down the
UPS.
To remotely control the UPS or view UPS information, use the escape key legend to control the
function normally controlled by the control panel softkeys. See Section 7.2 on page 93 for instructions
on navigating the control panel.
8.3.2 Event History Log
This key sequence prints the entire Event History Log of the UPS at the time the data is requested. The
printout begins with the oldest alarm entry in the queue and ends with the most recent. Any alarms
that occur while the Event History Log is printing are included in chronological order.