3.3 Inspecting and unpacking the UPS cabinet
The UPS cabinet is divided into two sections (825 kVA) or three sections (1100 kVA) which are palleted
separately for shipping.The cabinet is shipped bolted to a wooden pallet and protected with outer
protective packaging material (see Figure 3-16).
WARNING
The UPS cabinet is heavy (see Table 3-1 on page 13). If unpacking instructions are not closely
followed, the cabinet may tip and cause serious injury and equipment damage.
Do not install a damaged cabinet. Report any damage to the carrier and contact your service
representative immediately.
CAUTION
To prevent damage to the wiring channel and wiring in the UPM section base when lifting or
moving the cabinet:
•
Lift and move the 3 x UPM section using only the front or rear fork lift slots
•
Verify that the fork lift forks are in a horizontal position before inserting them into the fork
lift slots. DO NOT angle fork slots upward.
•
Insert the forks all the way through the base. DO NOT insert forks partially into the base to
move the cabinet.
•
Fork may be partially inserted into the front or rear fork lift slots for minor positioning if the
forks are kept in a horizontal position with no upward angling.
•
DO NOT use the fork lift slots on the end of the cabinet to move the cabinet.
If these instructions are not followed, damage to the wiring channel and wiring will occur.
1.
Carefully inspect the outer packaging for evidence of damage during transit.
NOTE
For the following step, verify that the forklift or pallet jack is rated to handle the weight of the
cabinet (see Table 3-1 on page 13 for cabinet weight).
2.
Use a forklift or pallet jack to move the packaged cabinets to the installation site, or as close as
possible, before unpacking. Insert the forklift or pallet jack forks from the right side of the cabinet,
between the supports on the bottom of the pallet (see Figure 3-12 on page 19 and Figure 3-13 on
page 20 for the location of the UPS center of gravity). If the cabinets must be moved using the
cabinet front or rear fork lift slots, see the caution statement at the beginning of this procedure.