3
1. Introduction to the Power Xpert® Release trip unit
PXR tRiP units foR PoweR Defense molDeD case ciRcuit bReakeRs
MN012007EN March 2019 www.eaton.com
motor protection settings
PXR 10 -mP
PXR 25 -mP
units
motor overload protection (l)
i
e
Full load amps (FLA)
10 settings
Variable
Amps
t
e
Motor trip class
5 settings 5 to 30
Variable
from 5 to 30
Seconds
Thermal memory
Enable/disable
Enable/disable
short circuit protection (s)
i
sd
Pickup
10 settings
3.0 to 13
Variable
from 3 to 13
x I
e
t
sd
Time selay dlat
3 settings
0.05, 0.15 or 0.30
Variable
from 0.05 to 0.50
Seconds
Zone selective interlock
Not available
Enable/disable
with visual indication
instantaneous protection (i)
i
i
Pickup
Fixed
(see settings tables)
Variable
from 3.0
x I
n
Ground (earth) fault protection (G)
i
g
Pickup – trip, alarm
only or OFF
Not available
Variable
from 0.20
x I
n
t
g
Time delay flat
Variable
from 0.10 to 1.0
Seconds
Thermal memory
Enable/disable
motor protection voltage functions
over voltage
Pickup
not available
Variable, 180 to 720
Volts
Time
Variable, 1 to 300
Seconds
under voltage
Pickup
not available
Variable, 60 to 670
Volts
Time
Variable, 1 to 300
Seconds
Voltage unbalance
Pickup
not available
Variable, 5 to 25
% of Volts
Time
Variable, 1 to 300
Seconds
current unbalance
Pickup
variable, 5 to 35
Variable, 5 to 25
% of Amps
Time
variable, 1 to 300
Variable, 1 to 300
Seconds
Phase loss
Pickup
Yes - use the current
Unbalance function
Fixed at 75
% of Amps
Time
Variable, 1 to 240
Seconds
Phase rotation
Configuration
Not available
ABC or CBA
Sequence
Time
Fixed at 200
Milliseconds
Reverse power
Pickup
Not available
Variable, 1 to 65,500
kW
Time
Variable, 1 to 300
Seconds
Each function can be set to: a) trip the breaker, b) alarm only, or c) be disabled (OFF)
neutral protection (n)
Described in line protection table above
General protection functions
Section
9 contains a detailed list of all available settings for each trip unit and breaker frame combination.
Light gray shaded settings are only configurable through the USB with PXPM software.
1.1.1 Time current curves
Time current curves (TCC) for every Power Defense circuit breaker within the PXR family of trip units are available at www.
eaton.com/powerdefense.