38
10 Available protection settings
PXR tRiP units foR PoweR Defense molDeD case ciRcuit bReakeRs
MN012007EN March 2019 www.eaton.com
10.2.6 PDC2 PXR10 – Motor protection settings (MLSI)
frame
63 a
100 a
160 a
200 a
220 a
all
63 a
100 a
160 a
200 a
220a
all
Profile
overload
short delay
Dial
fla = ie
trip profile
isd(x ie)
PXPm
setting
Pickup ie (full load amps)
trip class
at 6x (ie)
Phase unbal.
%
Pickup lsd = nx (ie)
time
(tsd)
a
16
25
40
50
63
5
No
3
3
3
3
3
Instanta
neous,
0.15s,
0.30s
b
18
32
50
63
80
10
4
4
4
4
4
c
20
40
63
80
90
15
5
5
5
5
5
D
25
50
70
90
100
20
6
6
6
6
6
e
32
55
80
100
125
30
7
7
7
7
7
f
40
63
90
125
150
5
Yes
5 to 35 %
1 to 200 sec
8
8
8
8
8
G
45
70
100
150
160
10
10
10
10
10
10
H
50
80
125
160
175
15
11
11
11
11
11
J
55
90
150
175
200
20
12
12
12
12
12
k
63
100
160
200
220
30
13
13
13
13
13
configurable using PXPm software
Instantaneous override:
1100 A
2100 A
Pickup (Isd) limited by Max Instantaneous
10.2.7 PDG2 PXR20 settings
frame
60 a
100 a
150 a
225 a
all
all
60 a
100 a
150 a
225 a
G styles
Profile
long delay
short delay
instantaneous
Ground
Dial
ir (a)
tr(s) @ 6x ir isd (x ir)
tsd (s)
ii (x in)
ig (x in)
tg (s)
setting
Pickup ir (amps)
time (s)
at 6x (lr)
Pickup (isd)
isd = nx (ir) tsd (s)
Pickup ii = nx (in)
Pickup (ig)
ig = nx (in)
time (tg)
tg (s)
a
15
32
50
80
0.5
1.5
0.050
2
2
2
2
0.2
0.100
b
16
35
60
90
1
2.0
0.100
3
3
3
3
0.3
0.150
c
20
40
63
100
2
3.0
0.150
4
4
4
4
0.4
0.200
D
25
50
70
110
4
4.0
0.200
5
5
5
5
0.6
0.300
e
30
60
80
125
7
5.0
0.300
6
6
6
6
0.8
0.500
f
35
63
90
150
10
6.0
0.400
8
7
8
7
1.0
0.750
G
40
70
100
160
12
8.0
0.500
10
8
10
8
0.2
1.000
H
45
80
110
175
15
10.0
0.067
12
9
12
9
0.5
0.067
J
50
90
125
200
20
12.0
0.150
15
10
13
9
1.0
0.150
k
60
100
150
225
24
OFF
0.3
18.3
11
14
9.3
OFF
0.300
Flat
Instantaneous override
Trip
Flat
I
2
t
1100 A
2100 A
Alarm
I
2
t