11 Modbus register map
PXR tRiP units foR PoweR Defense molDeD case ciRcuit bReakeRs
MN012007EN March 2019 www.eaton.com
Historical trip event
Register
format
R/w
Descriptions
units
408193
Encoded
R/W
Event type: trip = 80FF16/alarm = 81FF16
408194
Unsigned32
R
Earliest event ID
408196
Unsigned32
R
Latest event ID
408198
Unsigned32
R/W
Requested event ID
408200
Unsigned32
R
Previous event ID
408202
Unsigned32
R
Next event ID
408204
Date/time
R
Date/time
408212
Encoded
R
Format of data: trip = 0004
16
,
major alarm = 0005
16
408213
B15-b00
R
Object validity bits
408214
B31-b16
R
Object validity bits
408215
Encoded
R
Status cause (primary, secondary, cause)
408217
Unsigned32
R
IA
A
408219
Unsigned32
R
IB
A
408221
Unsigned32
R
IC
A
408223
Unsigned32
R
IN
A
408225
Unsigned32
R
IG source
A
408227
Unsigned32
R
IG residual
A
408229
Unsigned16
R
VAB
V
408230
Unsigned16
R
VBC
V
408231
Unsigned16
R
VCA
V
408232
Unsigned16
R
VAN
V
408233
Unsigned16
R
VBN
V
408234
Unsigned16
R
VCN
V
408235
Signed32
R
Real 3 phase power
W
408237
Signed32
R
Reactive 3 phase power
VAR
408239
Unsigned32
R
Apparent 3 phase power
VA
408241
Signed32
R
Real 3 phase power demand
W
408243
Signed32
R
Reactive 3 phase power demand
VAR
408245
Unsigned32
R
Apparent 3 phase power demand
VA
408247
Singed16
R
Device temperature
1/10 °C
408248
Unsigned16
R
Frequency
1/10 Hz
408249
Singed16
R
Apparent power factor
1/100 pf
408250
Unsigned16
R
Operations count
408251
B31-b00
R
Binary status with validity bits
Historical alarm
Register
format
R/w
Historical summary event
408193
Encoded
R/W
Event type: summary = 81FF
16
408194
Unsigned32
R
Earliest event ID
408196
Unsigned32
R
Latest event ID
408198
Unsigned32
R/W
Requested event ID
408200
Unsigned32
R
Previous event ID
408202
Unsigned32
R
Next event ID
408204
Date/time
R
Date/time
408212
Encoded
R
Format of data: minor alarm = 0006
16
408213
B0
R
Object validity bit
408214
Encoded
R
Status cause(primary, secondary, cause)
Note:
address 408225 and 408227 are both ground current. According to the set point ‘Ground Sensing’ setting in set
points group 1: protection group, the actual ground current would be displayed in related register and value in the other
register would be zero. For example, if the ‘Ground Sensing’ setting is 0, representing the ground current sensing type is
residual ground current. IG residual in address 408227 would be the actual value and IG source in address 408225 would
be zero.