10 Available protection settings
PXR tRiP units foR PoweR Defense molDeD case ciRcuit bReakeRs
MN012007EN March 2019 www.eaton.com
10.2.32 PDG5 PXR25 and 20D settings
frame
800 a 1200 a 1600 a iec 800 a 1200 a 1600 a iec
all
800 a
1200 a 1600 a iec
G styles
Profile
long Delay
short Delay
instantaneous
Ground
setting
Pickup ir (amps)
time (s)
at 6x (ir)
Pickup
(isd)
isd =nx (lr)
time
(tsd)
tsd (s)
Pickup li = nx (in)
Pickup (ig)
lg = nx
(in)
time
(tg)
tg (s)
min
320
500
800
0.5
0.5
0.5
1.5
0.050
2
2
2
0.2
0.100
max
800
1200
1600
14.0
24.0
20.0
8.0
0.500
18
12
9
1.0
1.000
min
0.5
0.5
0.5
0.067
0.2
0.067
max
7
7
7
0.300
1.0
0.300
step
10
10
10
0.10
0.10
0.10
0.10
0.01
0.10
0.10
0.01
0.01
add'l
opt
OFF
OFF
I
2
t
I
2
t
I
2
t
Flat
Instantaneous override
Trip
Flat
I
4
t
I
4
t
I
4
t
I
2
t
14400 A
Alarm
I
2
t
10.2.33 PDG6 PXR20 settings
frame
1600 a
2000 a 2500 a iec all
1600 a 2000 a 2500 a iec all
1600 a 2000 a 2500 a iec
G styles
Profile
long delay
short delay
instantaneous
Ground
Dial
ir (a)
tr(s)
@6x ir
isd (x lr)
tsd (s)
ii (x in)
ig (x in)
tg (s)
setting
Pickup ir (amps)
time (s)
at 6x (ir)
Pickup (isd)
isd =nx (lr)
time
(tsd)
tsd (s)
Pickup li = nx (in)
Pickup (ig)
lg = nx(in)
time
(tg)
tg (s)
1
700
1000
1600
0.5
1.5
1.5
1.5
0.050
2
2
2
0.2
0.100
2
800
1100
1700
1
2.0
2.0
2.0
0.100
3
3
2.5
0.3
0.150
3
900
1200
1800
2
3.0
3.0
2.5
0.150
4
4
3
0.4
0.200
4
1000
1250
1900
4
4.0
4.0
3.0
0.200
5
5
3.5
0.6
0.300
5
1100
1400
2000
7
5.0
5.0
3.5
0.300
6
6
4
0.8
0.500
6
1200
1600
2100
10
6.0
6.0
4.0
0.400
7
7
4.5
1.0
0.750
7
1250
1700
2200
12
7.0
7.0
4.5
0.500
8
7.5
5
0.2
1.000
8
1400
1800
2300
15
8.0
8.0
5.0
0.067
9
8
6
0.5
0.067
9
1500
1900
2400
20
9.0
9.0
6.0
0.150
10
8.5
7
1.0
0.150
10
1600
2000
2500
24
OFF
OFF
OFF
0.300
10.94
8.75
7.00
OFF
0.300
Flat
Instantaneous override
Trip
Flat
I
2
t
17500 A
Alarm
I
2
t
Pickup (Isd) limited by Max Instantaneous
Note that ground fault pickup will not exceed 1200 A.
10.2.34 PDG6 PXR25 and 20D settings
frame
1600 a 2000 a 2500 a iec all
1600 a 2000 a 2500 a iec all
800 a 1200 a 1600 a iec
G styles
Profile
long delay
short delay
instantaneous
Ground
setting
Pickup ir (amps)
time (s)
at 6x (ir)
Pickup (isd)
isd =nx (lr)
time
(tsd)
tsd (s)
Pickup li = nx (in)
Pickup (ig)
lg = nx (in)
time
(tg)
tg (s)
min
700
1000
1600
0.5
1.5
1.5
1.5
0.050
2
2
2
0.2
0.100
max
1600
2000
2500
24.0
9.0
9.0
6.0
0.500
10.94
8.75
7.00
1.0
1.000
min
0.5
0.067
0.2
0.067
max
7
0.300
1.0
0.300
step
10
10
10
0.10
0.10
0.10
0.10
0.01
0.10
0.10
0.10
0.01
0.01
add'l
opt
OFF
OFF
OFF
OFF
I
2
t
Flat
Instantaneous override
Trip
Flat
I
4
t
I
2
t
17500 A
Alarm
I
2
t
Pickup (Isd) limited by Max Instantaneous
Note that ground fault pickup will not exceed 1200 A.