10 Available protection settings
PXR tRiP units foR PoweR Defense molDeD case ciRcuit bReakeRs
MN012007EN March 2019 www.eaton.com
10.2.8 PDC2 PXR20 settings
frame
63 a 100 a 160 a 200 a 250 a all
all
63 a 100 a 160 a 200 a 250 a
G styles
Profile
long delay
short delay
instantaneous
Ground
Dial
ir (a)
tr(s)
@6x ir
isd (x lr)
tsd (s)
ii (x in)
ig (x in)
tg (s)
setting
Pickup ir (amps)
time (s)
at 6x (ir)
Pickup
(isd)
isd =nx (lr)
time (tsd)
tsd (s)
Pickup li = nx (in)
Pickup (ig)
lg = nx (in)
time (tg)
tg (s)
a
16
25
40
50
63
0.5
1.5
0.050
2
2
2
2
2
0.2
0.100
b
18
32
50
63
80
1
2.0
0.100
3
3
3
3
3
0.3
0.150
c
20
40
63
80
100
2
3.0
0.150
4
4
4
4
4
0.4
0.200
D
25
50
70
90
125
4
4.0
0.200
5
5
5
5
5
0.6
0.300
e
32
55
80
100
150
7
5.0
0.300
6
6
6
6
6
0.8
0.500
f
40
63
90
125
160
10
6.0
0.400
8
7
8
7
6.5
1.0
0.750
G
45
70
100
150
175
12
8.0
0.500
10
8
10
8
7
0.2
1.000
H
50
80
125
160
200
15
10.0
0.067
12
9
12
9
7.5
0.5
0.067
J
55
90
150
175
225
20
12.0
0.150
15
10
13
10
8
1.0
0.150
k
63
100
160
200
250
24
OFF
0.3
17.5
11
13.125 10.5
8.4
OFF
0.300
Flat
Instantaneous override
Trip
Flat
I
2
t
1100 A
2100 A
Alarm
I
2
t
10.2.9 PDG2 PXR25 and 20D settings
frame
60 a
100 a 150 a 225 a all
all
60 a
100 a 150 a 225 a
G styles
Profile
long delay
short delay
instantaneous
Ground
setting
Pickup ir (amps)
time (s)
at 6x (ir
Pickup (isd)
isd =nx (lr)
time (tsd)
tsd (s)
Pickup li = nx (in)
Pickup (ig)
lg = nx (in)
time (tg)
tg (s)
min
15
25
50
80
0.5
1.5
0.050
2
2
2
2
0.2
0.100
max
60
100
150
225
24
12.0
0.500
18.3
11
14
9.3
1.0
1.000
min
0.5
0.067
0.2
0.067
max
7
0.300
1.0
0.300
step
1
1
1
1
0.10
0.10
0.010
0.10
0.10
0.10
0.10
0.010
0.010
add'l opt
OFF
OFF
I²t
Flat
Instantaneous override
Trip
Flat
I
4
t
I
2
t
1100 A
2100 A
Alarm
I
2
t
10.2.10 PDG2 PXR25 – Motor protection settings
frame
60 a
100 a 150 a 225 a
all
all
60 a
100 a
150 a
225 a
G styles
Profile
overload
short delay
instantaneous
Ground
setting
Pickup ie (full load amps)
trip class
at 6x (ie)
Pickup (isd)
lsd = nx (ie)
time (tsd)
tsd (s)
Pickup li = nx (in)
Pickup (ig)
lg = nx (in)
time (tg)
tg (s)
min
15
25
50
80
0.5
3.0
0.050
3
3
3
3
0.2
0.100
max
60
100
150
225
30
13.0
0.500
18.3
11
14
9.3
1.0
1.000
min
0.2
0.067
max
1.0
0.300
step
1.00
1.00
1.00
1.00
0.10
0.10
0.01
0.10
0.10
0.10
0.10
0.01
0.01
add'l opt
OFF
OFF
Flat
Instantaneous override
Trip
Flat
1100 A
2100 A
Alarm
Pickup (Isd) limited by Max Instantaneous