04/10 MN04020001Z-EN
Parameter menu (PAR)
93
P6.24
509
-
Frequency jump 1, lower value (
a
).
0.00
0.00 - P6.4 Hz
P6.25
510
-
Frequency jump 1, upper value (
b
).
0.00
P6.26
511
-
Frequency jump 2, lower value (
a
).
0.00
0.00 - P6.4 Hz
P6.27
512
-
Frequency jump 2, upper value (
b
).
0.00
0.00 - P6.4 Hz
P6.28
513
-
Frequency jump 3, lower value (
a
).
0.00
0.00 - P6.4 Hz
P6.29
514
-
Frequency jump 3, upper value (
b
).
0.00
0.00 - P6.4 Hz
91
a
: P6.24, P6.26, P6.28
b
: P6.25, P6.27, P6.29
In systems with mechanical resonances, you can cut out these
frequency ranges for stationary operation. Up to three different
frequency ranges can be set.
Figure 83:
Setting range for frequency masking
PNU
ID
Access right
RUN
Value
Description
Factory setting
(P1.3)
P6.30
759
-
REAF, number of automatic restarts.
3
1 - 10
You can define here the permissible number of automatic restarts
(REAF = Restart After Failure).
P6.31
1481
-
Manual mode, control level
1
Assignment of the control levels as per P6.1.
Manual mode is activated via parameter P3.37.
P6.32
1482
Manual mode, setpoint source
3
Assignment of setpoint sources as per P6.2.
Manual mode is activated via parameter P3.37.
P6.33
1483
Manual mode, KEYPAD blocked.
1
The Start/Stop functions are blocked in Manual mode via the
keypad.
0
Deactivated
1
Activated
PNU
ID
Access right
RUN
Value
Description
Factory setting
(P1.3)
f
Hz
a
b
t
Содержание M-Max series
Страница 8: ...04 10 MN04020001Z EN 4...
Страница 12: ...04 10 MN04020001Z EN 8...
Страница 58: ...04 10 MN04020001Z EN 54...
Страница 66: ...04 10 MN04020001Z EN 62...
Страница 138: ...04 10 MN04020001Z EN 134...
Страница 150: ...04 10 MN04020001Z EN 146...
Страница 196: ...04 10 MN04020001Z EN 192...