04/10 MN04020001Z-EN
Modbus Process Data
143
Status word (ID 2101)
Information on the device status and messages are defined in the
status word:
General status word (ID 2102)
Actual speed (frequency actual value)
The actual speed of the frequency inverter is within a value range
of 0 and 10,000. In the application, this value is scaled to a
percentage in the frequency range between the defined minimum
and maximum frequencies.
Bit
Description
Value = 0
Value = 1
0
Drive not ready
Ready for operation (READY)
1
Stop
Running operation message (RUN)
2
Clockwise rotating field (FWD)
Anticlockwise rotating field (REV)
3
No fault
Fault detected (FAULT)
4
No warning
Warning active (ALARM)
5
Acceleration ramp
Frequency actual value equals setpoint value definition
6
-
Zero speed
7
Speed control deactivated
Speed control activated
8 - 15
Not used
Bit
Description
Value = 0
Value = 1
0
-
Control level = Fieldbus (BUS)
1
-
Setpoint input = Fieldbus (BUS)
2 - 10
Not used
11
Remote input not active
Remote input active
The status of a selected digital input (P3.28) is read out.
12
Actuation (P3.37) not active
Actuation (P3.37) active
13
-
Control level = Control signal terminals (I/O)
14
-
Control level = KEYPAD
15
-
Control level = Fieldbus (BUS)
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
MSB
LSB
Содержание M-Max series
Страница 8: ...04 10 MN04020001Z EN 4...
Страница 12: ...04 10 MN04020001Z EN 8...
Страница 58: ...04 10 MN04020001Z EN 54...
Страница 66: ...04 10 MN04020001Z EN 62...
Страница 138: ...04 10 MN04020001Z EN 134...
Страница 150: ...04 10 MN04020001Z EN 146...
Страница 196: ...04 10 MN04020001Z EN 192...