![Eaton M-Max series Скачать руководство пользователя страница 193](http://html1.mh-extra.com/html/eaton/m-max-series/m-max-series_operating-instructions-manual_3922029193.webp)
04/10 MN04020001Z-EN
List of parameters
189
Second parameter set
P14.1
1347
-
rw
Motor (2PS),
rated current limit
0.2 x I
e
- 2 x I
e
(
h
Motor rating plate)
I
e
P14.2
1352
-
rw
Current (2PS)
0.2 x I
e
- 2 x I
e
1.5 x I
e
P14.3
1350
-
rw
Motor (2PS) nominal speed
300 … 20000 min
-1
(
h
Motor rating plate)
1440
1720
P14.4
1351
-
rw
Motor (2PS),
power factor (cos
v
)
0.30 - 1.00
(
h
Motor rating plate)
0.85
P14.5
1348
-
rw
Motor (2PS),
rated voltage
180 - 500 V
(
h
Motor rating plate)
124
230
400
P14.6
1349
-
rw
Motor (2PS), nominal
frequency
30 - 320 Hz
(
h
Motor rating plate)
124
50.00
60.00
P14.7
1343
-
rw
Minimum frequency (2PS)
0.00 - P14.8 Hz
124
0.00
P14.8
1344
-
rw
Maximum frequency (2PS)
P14.7 - 320.00 Hz
124
50.00
60.00
P14.9
1345
-
rw
Acceleration time (acc3)
0.1 - 3000 s
124
3.0
P14.10
1346
-
rw
Deceleration time (dec3)
0.1 - 3000 s
124
3.0
P14.11
1355
-
rw
U/f characteristic curve
[2PS]
0 = Linear
1 = Quadratic
2 = Configurable
124
0
P14.12
1354
-
rw
Torque increase (2PS)
0 = Deactivated
1 = activated
125
0
P14.13
1353
-
rw
Motor (2PS),
temperature protection
0 = Deactivated
1 = Warning
2 = Error, stop according to P6.8
125
0
P14.14
1469
-
rw
Motor (2PS),
ambient temperature
-20 - +100 °C
125
40
P14.15
1470
-
rw
Motor (2PS),
cooling factor at zero
frequency
0.0 - 150 %
125
40.0
P14.16
1471
-
rw
Motor (2PS),
thermal time constant
1 - 200 min
125
45
PNU
ID
Access right
Designation
Value range
Page
FS
(P1.3)
User
setting
RUN
ro/rw
Содержание M-Max series
Страница 8: ...04 10 MN04020001Z EN 4...
Страница 12: ...04 10 MN04020001Z EN 8...
Страница 58: ...04 10 MN04020001Z EN 54...
Страница 66: ...04 10 MN04020001Z EN 62...
Страница 138: ...04 10 MN04020001Z EN 134...
Страница 150: ...04 10 MN04020001Z EN 146...
Страница 196: ...04 10 MN04020001Z EN 192...