Serial interface (Modbus RTU)
04/10 MN04020001Z-EN
142
General control word (ID 2002)
Speed setpoint (ID 2003; frequency setpoint)
The permitted value range lies between 0 and 10.000. In the
application, this value is scaled to a percentage in the frequency
range between the defined minimum and maximum frequencies.
Output process data
The output process data is used to monitor the frequency inverter.
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
NB
NB
NB
NB
NB
NB
NB
NB
NB
NB
NB
NB
NB
NB
NB
NB
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
MSB
LSB
ID
MODBUS register
Designation
Value range
Type
2101
32101, 42101
Fieldbus status word
-
Binary code
2102
32102, 42102
Fieldbus general status word
-
Binary code
2103
32103, 42103
Fieldbus actual speed
0.01
%
2104
32104, 42104
Motor frequency
0.01
+/- Hz
2105
32105, 42105
Motor speed
1
+/- rpm (min
-1
)
2106
32106, 42106
Motor current
0.01
A
2107
32107, 42107
Motor torque
0.1
+/- % (of the nominal value)
2108
32108, 42108
Motor power
0.1
+/- % (of the nominal value)
2109
32109, 42109
Motor voltage
0.1
V
2110
32110, 42110
DC-link voltage (DC)
1
V
2111
32111, 42111
Current error
-
Error code (E...)
Содержание M-Max series
Страница 8: ...04 10 MN04020001Z EN 4...
Страница 12: ...04 10 MN04020001Z EN 8...
Страница 58: ...04 10 MN04020001Z EN 54...
Страница 66: ...04 10 MN04020001Z EN 62...
Страница 138: ...04 10 MN04020001Z EN 134...
Страница 150: ...04 10 MN04020001Z EN 146...
Страница 196: ...04 10 MN04020001Z EN 192...