Appendix
04/10 MN04020001Z-EN
174
Block Transformatoren-Elektronik GmbH & Co. KG
Postfach 11 70
27261 Verden
Max-Planck-Straße 36 - 46
Telefon: (0 42 31) 6 78-0
Telefax: (0 42 31) 6 78-1 77
E-Mail:
Internet:
www.block-trafo.de
DF51-
Maximum
output voltage
Rated
operational
current
(motor
current)
I
e
[A]
Assigned
sine-wave
filter
320-4K0
3 ~ 240 V + 10 %
17.5
SFB 400/16.5
1)
(SFB 400/23.5)
320-5K5
24
SFB 400/23.5
320-7K5
32
SFB 400/32
322-025
1.6
SFB400/4
322-037
2.6
322-055
3
322-075
4
322-1K1
5
SFB400/10
322-1K5
8
322-2K2
11
SFB400/10
1)
(SFB 400/16.5)
340-037
3 ~ 480 V + 10 %
1.5
SFB400/4
340-075
2.5
340-1K5
3.5
340-2K2
5.5
SFB400/10
340-3K0
7.8
340-4K0
8.6
340-5K0
13
SFB400/16.5
340-7K5
16
1) At continuous 100 % motor load, use a sinusoidal filter of the next
higher (current) rating here.
Protection type
IP00, suitable for flush mounting in
devices and systems
Typical voltage drop
3 x 30 V
Frequency range
0 - 120 Hz
Permissible pulse frequency
3 - 8 kHz, fixed
Ambient temperature
F
40 °C
Approvals
c-UL-US
h
For more technical data for the SFB400/… series
sine-wave filters, see the manufacturer’s instructions.
Содержание M-Max series
Страница 8: ...04 10 MN04020001Z EN 4...
Страница 12: ...04 10 MN04020001Z EN 8...
Страница 58: ...04 10 MN04020001Z EN 54...
Страница 66: ...04 10 MN04020001Z EN 62...
Страница 138: ...04 10 MN04020001Z EN 134...
Страница 150: ...04 10 MN04020001Z EN 146...
Страница 196: ...04 10 MN04020001Z EN 192...