O & M Manual IM05805020K

             EATON LMR Plus

Effective September 2013

Electric Fire Pump Controllers

Page 5

www.chfire.com

EATON CORPORATION

Phase  Failure,  Fail  to  Start,  Undervoltage, 

Overvoltage, Low Room Temperature, Locked Rotor 

Trip,  Low  Suction  Pressure,  Auto  Shutdown 

Enabled,  Source  2  Disconnected  and  two  (2)  user 

defined LEDs.

There  are  nine  input  functions  accessible  via  the 

pushbuttons:

Silence Alarm

Motor Test

Data | Print

Lamp Test

Reset | Save/Exit

Up

Down

Ack. Alarm

Menu

A  four-line,  40-character  alphanumeric  LCD  Display 

module  is  used  to  display  all  LMR  Plus  monitored 

parameters,  set  points,  and  messages  in  easy  to  read 

formats.  The  display  has  a  green  high  contrast 

background that allows clear visibility of any information 

displayed.  The  display  is  continuously  lit  for  clear 

visibility under poorly lit or no light conditions.
Seven different displays can be presented via the LCD 

display:

Status Display

Set Points Display

Statistics Display

Diagnostics Display

Configuration Menu

Data/Print Menu

Message History Display

The  "Home"  screen  display  will  show  the  voltages  and 

currents on all three phases, system frequency, system 

pressure, and the current date and time. The fourth line 

of the display will also indicate the time remaining on any 

active  timers,  alarms  without  an  associated  LED,  and 

custom messages.

3.2.1 The LEDs

Power On -

  This  green  LED  will  be  illuminated 

when  there  is  power  present  in  the  controller  and 

the microprocessor board is powered up.

Pump Running -

 This green LED will be illuminated 

once the amperage draw in the controller exceeds 

20% of the programmed motor full load amps.

Local Start -

  This  green  LED  will  be  illuminated 

when the pump is running after the start pushbutton 

on the flange has been depressed.

Remote Start -

 This green LED will be illuminated 

when  the  pump  is  running  after  receiving  a  start 

signal on the remote start input.

Deluge Valve -

 This green LED will be illuminated 

when  the  pump  is  running  after  receiving  a  start 

signal  from  special  starting  equipment.  This  is  a 

normally  closed  contact  that  is  required  to  be 

opened to start.

Emergency Start -

  This  green  LED  will  be 

illuminated  when  the  pump  is  running  after  the 

emergency  start  handle  has  been  depressed  and 

the micro-switch has been activated.

Interlock On -

 This green LED will flash when the 

interlock  input  is  received,  signaling  that  another 

controller or device has locked out the controller.

Low Pressure -

 This green LED will flash when the 

system  pressure  has  dropped  below  the 

programmed low-pressure set point. If the pump is 

running  due  to  a  low-pressure  condition,  this  LED 

will be fully illuminated.

Auto Shutdown Enabled -

 This Green LED will be 

illuminated  when  the  Auto  Shutdown  function  is 

enabled.

Phase Reversal -

 This red LED will be illuminated 

when  the  controller  senses  that  the  input  voltage 

lines  are  reversed  and  there  is  a  risk  of  operating 

the pump in the reverse direction.

Phase Failure -

  This  red  LED  will  be  illuminated 

when at least one of the three phases coming into 

the controller is missing or the voltage is abnormally 

low.

Fail To Start -

 This red LED will be illuminated if the 

amperage draw has not reached 20% of the motor 

full  load  amps  after  the  programmed  fail  to  start 

timer has timed out.

Undervoltage -

  This  red  LED  will  illuminate  when 

the  system  voltage  is  below  the  programmed 

undervoltage alarm.

Overvoltage - 

This red LED will illuminate when the 

system  voltage  is  above  the  programmed 

overvoltage alarm.

Low Room Temperature -

  This  red  LED  will 

illuminate  when  the  low  room  temperature  signal 

has been received. A thermostat can be supplied as 

option R4.

Locked Rotor Trip -

  This  red  LED  will  illuminate 

when  the  controller  has  tripped  in  a  locked  rotor 

condition.

Low Suction Pressure/Low Foam Level -

 This red 

LED  will  illuminate  when  the  low  suction  pressure 

signal  has  been  received.  A  low  suction  pressure 

switch can be added to the controller as option P7.

Source 2 Disconnected -

  This  red  LED  will 

illuminate if the main disconnect switch on a transfer 

switch controller is turned off while the controller is 

energized.

Содержание LMR PLUS

Страница 1: ...EATON LMR Plus Electric Fire Pump Controllers O M Manual IM05805020K Effective September 2013...

Страница 2: ...A MAIN MENU TREE 16 APPENDIX B LANGUAGE MENU TREE 17 APPENDIX C REGIONAL SETTINGS MENU TREE 18 APPENDIX D PRESSURE SETTINGS MENU TREE 19 APPENDIX E TIMER VALUES MENU TREE 20 APPENDIX F ALARM SETPOINT...

Страница 3: ...ross the Line FD40 Part Winding FD50 Primary Resistor FD60 Autotransformer FD70 Wye Delta Star Delta Open Transition FD80 Wye Delta Star Delta Closed Transition FD90 Soft Start and FDM30 Medium Voltag...

Страница 4: ...controller isolated and the Start Pressure and Stop Pressure values programmed energize the controller If the system water pressure is lower than the start pressure the pump will start If the controll...

Страница 5: ...mp is running after receiving a start signal from special starting equipment This is a normally closed contact that is required to be opened to start Emergency Start This green LED will be illuminated...

Страница 6: ...ns When navigating the main display the enter button will allow the user to enter exit the message history statistics and diagnostics When in the menu system the enter button will allow the user to ch...

Страница 7: ...nge 4 2 2 Automatic Start Sequence Automatic start is defined as a low pressure condition deluge valve start or a pump start Whenever the motor is running via an automatic start the motor can automati...

Страница 8: ...tion time delay It will then switch the motor over to full voltage Phase Failure This relay is used for remote monitoring of a phase failure alarm condition In order to ensure dependable operation of...

Страница 9: ...s Pressure Settings Appendix D Pressure Sensor Enabled Enabled Disabled Drain Valve Enabled Enabled Disabled Pressure Start Point 100 PSI 0 500 PSI Pressure Stop Point 110 PSI 0 500 PSI Low Pressure A...

Страница 10: ...ted a delay timer Range 0 30 Seconds Default 10 Seconds must be set The controller will then verify if the input is still active every time the timer times out If the input is still active the timer w...

Страница 11: ...efore alarming on Overvoltage Once the condition no longer exists the alarm will automatically clear Undervoltage UV An Undervoltage setting is built into the controller If the system voltage is below...

Страница 12: ...motor until after an adjustable timer period has elapsed The Load Shed Timer will become active once the Load Shed function is enabled If the emergency input is not active the pump will start normall...

Страница 13: ...h the controller The diagnostics can be viewed on the main display saved to a USB storage device or viewed on the optional embedded webpage In order to view the diagnostics on the display press the up...

Страница 14: ...ing Modbus COM Option must be ordered for this function 7 4 RS232 Serial Port This optional port is used with the optional printer X1 to initiate a print cycle COM Option must be ordered for this func...

Страница 15: ...Note All cells need to be formatted as text Number of Hours Run 3 Column C is used to enter the number of hours the pump has run before the message will appear The format is as follows XXXXX Number o...

Страница 16: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 16 APPENDIX A MAIN MENU TREE...

Страница 17: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 17 www chfire com EATON CORPORATION APPENDIX B LANGUAGE MENU TREE...

Страница 18: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 18 APPENDIX C REGIONAL SETTINGS MENU TREE...

Страница 19: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 19 www chfire com EATON CORPORATION APPENDIX D PRESSURE SETTINGS MENU TREE...

Страница 20: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 20 APPENDIX E TIMER VALUES MENU TREE...

Страница 21: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 21 www chfire com EATON CORPORATION APPENDIX F ALARM SETPOINTS MENU TREE...

Страница 22: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 22 APPENDIX G CUSTOMER INPUT OUTPUT MENU TREE...

Страница 23: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 23 www chfire com EATON CORPORATION APPENDIX G A CUSTOM INPUTS MENU TREE...

Страница 24: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 24 APPENDIX G B CUSTOM OUTPUTS MENU TREE...

Страница 25: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 25 www chfire com EATON CORPORATION APPENDIX G C CUSTOM LIGHTS MENU TREE...

Страница 26: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 26 APPENDIX H MAIN MENU PASSWORD MENU TREE...

Страница 27: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 27 www chfire com EATON CORPORATION APPENDIX J CUSTOM MESSAGE LOAD ACTIVATION...

Страница 28: ...25 30 40 60 75 1 14 1 0 Per CU AL 1 14 2 0 CU AL 40 50 75 100 100 1 4 4 0 Per CU 1 4 350MCM CU AL 75 75 150 200 200 1 3 350MCM Per CU AL 1 4 350MCM CU AL 100 125 200 250 300 2 3 0 250MCM Per CU AL 2 1...

Страница 29: ...shutdown after receiving a low foam level signal LOW PRESSURE The system pressure has dropped below the programmed pressure start point LOW PRESSURE ALARM The system pressure has dropped below the pr...

Страница 30: ...TUP Power has been reapplied to the system and a successful system boot has been completed TRANSDUCER FAILURE The controller has detected that the transducer has failed TRANSDUCER OK The controller ha...

Страница 31: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 31 www chfire com EATON CORPORATION NOTES...

Страница 32: ...o and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and EATON NO WARRANTIES EX...

Отзывы: