O & M Manual IM05805020K

             EATON LMR Plus

Effective September 2013

Electric Fire Pump Controllers

EATON CORPORATION

www.chfire.com

Page 12

Link to Light - 

All inputs can be linked to one of the 

future LED's. If the LED is already linked to another 

input  or  is  programmed  for  another  alarm,  the 

program will show that the LED is programmed for 

another  alarm  and  ask  if  the  LED  should  be 

reassigned. Default value is Disabled.

Latched Until Reset - 

The  alarm  signal  can  be 

programmed  to  latch  in an  on  state  until the ACK/

ALARM or RESET buttons are pressed. In this case 

if there are any associated relays or LED's linked to 

the input, they will stay active until the ACK/ALARM 

or RESET buttons are pressed. Default value is No.

Normal Input State - 

All inputs can be programmed 

as normally open or normally closed. Default value 

is Open.

Timer - 

A  timer  can  be  programmed  to  delay  the 

time before the alarm becomes active. Default value 

is  0  seconds.  Range  is  0-500  seconds.  The  timer 

will reset if the input is removed before the time has 

timed out.

Custom Outputs - 

The optional output relays, as well as 

the  Future  #1,  relay  can  be  programmed  to  operate 

based on generic values. The Custom Output Menu will 

display  each  output,  what  it  is  programmed  for  and  if 

there  are  any  associated  future  inputs  and  /  or  lights 

linked  to  the  output.  Please  refer  to  Table  3  for  the 

generic values the optional outputs can be programmed 

for. Following is a description of the menu items in the 

Custom Outputs menu.

Table 3 Generic Outputs

Load Shed - 

When  an  output  is  programmed  for 

Load  Shed  and  there  is  any  call  to  start,  except 

remote  start,  local  start  and  emergency  start,  the 

program  will  scan  the  Transfer  Switch  Emergency 

Input, terminal 58.  If this input is active, the program 

will energize the assigned output relay and delay the 

start of the motor until after an adjustable timer period 

has  elapsed.    The  Load  Shed  Timer  will  become 

active once the Load Shed function is enabled.  If the 

emergency  input  is  not  active,  the  pump  will  start 

normally.  The load shed relay will return to its normal 

state once the timer has finished timing.

Load Shed Timer - 

This timer will delay the starting 

of the motor for a programmed set time as outlined 

in  the  previous  item.    While  timing,  the  remaining 

time  will  be  displayed  on  the  fourth  line  of  the 

display.

Latched Until Reset - 

Output relays can be set as 

latching  relays.  Pressing  the  ACK/ALARM  or 

RESET  buttons  will  unlatch  them.  Default  value  is 

No.

Fail Safe -

  Output  relays  can  be  programmed  to 

energize  under  normal  conditions  (fail  safe)  or  de-

energize  under  normal  conditions.  Default  value  is 

No.

Timer -

 Each output relay can be programmed as a 

time delay relay. Either as an On delay or as an Off 

delay. If it is set for On Delay (default) the relay will 

delay for the programmed time prior to activating the 

relay. If it is set for Off Delay the relay will activate 

the  relay  instantly  and  then  de-activate  it  after  the 

programmed time.

Custom Lights - 

The  two  (2)  optional  LED's  can  be 

programmed for alarms that do not have an associated 

LED or one of the custom inputs. In this section of the 

program, the LED's can be programmed for one of the 

values  listed  in  Table  4.  As  a  default  the  LED's  will  be 

programmed for Undefined. 

Table 4 Custom Lights

Alarm

Low Pressure
High Pressure
Overvoltage
Undervoltage
Low Suction
Interlock On
Fail To Start
Pump Running
Motor Overload
Weekly Test Timing
Call to Start
Over Frequency
Under Frequency
Local Start
Remote Start
Deluge Start
Emergency Start
Low Pressure Start
Pump Start
RPT Timing
Sequential Start Timing
Transducer Failure
Backup Battery Low
Low Room Temp

Load Shed
Fail to Stop

Alarm

High Pressure
Motor Overload
Weekly Test Timing
Over Frequency
Under Frequency
RPT Timing
Sequential Start Timing
Transducer Failure
Pump Start
Battery Backup Low
Fail to Stop

Alarm

Содержание LMR PLUS

Страница 1: ...EATON LMR Plus Electric Fire Pump Controllers O M Manual IM05805020K Effective September 2013...

Страница 2: ...A MAIN MENU TREE 16 APPENDIX B LANGUAGE MENU TREE 17 APPENDIX C REGIONAL SETTINGS MENU TREE 18 APPENDIX D PRESSURE SETTINGS MENU TREE 19 APPENDIX E TIMER VALUES MENU TREE 20 APPENDIX F ALARM SETPOINT...

Страница 3: ...ross the Line FD40 Part Winding FD50 Primary Resistor FD60 Autotransformer FD70 Wye Delta Star Delta Open Transition FD80 Wye Delta Star Delta Closed Transition FD90 Soft Start and FDM30 Medium Voltag...

Страница 4: ...controller isolated and the Start Pressure and Stop Pressure values programmed energize the controller If the system water pressure is lower than the start pressure the pump will start If the controll...

Страница 5: ...mp is running after receiving a start signal from special starting equipment This is a normally closed contact that is required to be opened to start Emergency Start This green LED will be illuminated...

Страница 6: ...ns When navigating the main display the enter button will allow the user to enter exit the message history statistics and diagnostics When in the menu system the enter button will allow the user to ch...

Страница 7: ...nge 4 2 2 Automatic Start Sequence Automatic start is defined as a low pressure condition deluge valve start or a pump start Whenever the motor is running via an automatic start the motor can automati...

Страница 8: ...tion time delay It will then switch the motor over to full voltage Phase Failure This relay is used for remote monitoring of a phase failure alarm condition In order to ensure dependable operation of...

Страница 9: ...s Pressure Settings Appendix D Pressure Sensor Enabled Enabled Disabled Drain Valve Enabled Enabled Disabled Pressure Start Point 100 PSI 0 500 PSI Pressure Stop Point 110 PSI 0 500 PSI Low Pressure A...

Страница 10: ...ted a delay timer Range 0 30 Seconds Default 10 Seconds must be set The controller will then verify if the input is still active every time the timer times out If the input is still active the timer w...

Страница 11: ...efore alarming on Overvoltage Once the condition no longer exists the alarm will automatically clear Undervoltage UV An Undervoltage setting is built into the controller If the system voltage is below...

Страница 12: ...motor until after an adjustable timer period has elapsed The Load Shed Timer will become active once the Load Shed function is enabled If the emergency input is not active the pump will start normall...

Страница 13: ...h the controller The diagnostics can be viewed on the main display saved to a USB storage device or viewed on the optional embedded webpage In order to view the diagnostics on the display press the up...

Страница 14: ...ing Modbus COM Option must be ordered for this function 7 4 RS232 Serial Port This optional port is used with the optional printer X1 to initiate a print cycle COM Option must be ordered for this func...

Страница 15: ...Note All cells need to be formatted as text Number of Hours Run 3 Column C is used to enter the number of hours the pump has run before the message will appear The format is as follows XXXXX Number o...

Страница 16: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 16 APPENDIX A MAIN MENU TREE...

Страница 17: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 17 www chfire com EATON CORPORATION APPENDIX B LANGUAGE MENU TREE...

Страница 18: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 18 APPENDIX C REGIONAL SETTINGS MENU TREE...

Страница 19: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 19 www chfire com EATON CORPORATION APPENDIX D PRESSURE SETTINGS MENU TREE...

Страница 20: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 20 APPENDIX E TIMER VALUES MENU TREE...

Страница 21: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 21 www chfire com EATON CORPORATION APPENDIX F ALARM SETPOINTS MENU TREE...

Страница 22: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 22 APPENDIX G CUSTOMER INPUT OUTPUT MENU TREE...

Страница 23: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 23 www chfire com EATON CORPORATION APPENDIX G A CUSTOM INPUTS MENU TREE...

Страница 24: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 24 APPENDIX G B CUSTOM OUTPUTS MENU TREE...

Страница 25: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 25 www chfire com EATON CORPORATION APPENDIX G C CUSTOM LIGHTS MENU TREE...

Страница 26: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 26 APPENDIX H MAIN MENU PASSWORD MENU TREE...

Страница 27: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 27 www chfire com EATON CORPORATION APPENDIX J CUSTOM MESSAGE LOAD ACTIVATION...

Страница 28: ...25 30 40 60 75 1 14 1 0 Per CU AL 1 14 2 0 CU AL 40 50 75 100 100 1 4 4 0 Per CU 1 4 350MCM CU AL 75 75 150 200 200 1 3 350MCM Per CU AL 1 4 350MCM CU AL 100 125 200 250 300 2 3 0 250MCM Per CU AL 2 1...

Страница 29: ...shutdown after receiving a low foam level signal LOW PRESSURE The system pressure has dropped below the programmed pressure start point LOW PRESSURE ALARM The system pressure has dropped below the pr...

Страница 30: ...TUP Power has been reapplied to the system and a successful system boot has been completed TRANSDUCER FAILURE The controller has detected that the transducer has failed TRANSDUCER OK The controller ha...

Страница 31: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 31 www chfire com EATON CORPORATION NOTES...

Страница 32: ...o and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and EATON NO WARRANTIES EX...

Отзывы: