Eaton LMR PLUS Скачать руководство пользователя страница 8

O & M Manual IM05805020K

             EATON LMR Plus

Effective September 2013

Electric Fire Pump Controllers

EATON CORPORATION

www.chfire.com

Page 8

programmed for Low Suction Shutdown it will initiate the 

shutdown sequence. Refer to Section 5 to program Low 

Suction  Shutdown.  When  the  controller  is  setup  for  a 

foam  system,  all  references  to  Low  Suction  Shutdown 

will be changed to Low Foam Level.

Low Room Temperature (Terminal 38)

When  this  input  is  in  the  "Connected"  state,  the  LMR 

Plus controller will signal a visual indication on the main 

display board for Low Room Temperature. The Common 

Alarm relay will also de-energize for remote monitoring 

of this alarm.

Interlock On (Terminal 39)

When  this  input  is  in  the  "Connected"  state,  the  LMR 

Plus controller will not permit a start of the motor except 

for  Emergency  Start.  This  input  is  typically  used  in 

backup style systems. For example, the Engine Running 

contacts  from  the  backup  Diesel  Engine  Controller  are 

wired into this input. When the Diesel Engine is running, 

it  will  lock  out  the  LMR  Plus  panel  and  prevent  it  from 

starting.

Inputs (Terminals 40 to 48)

These are programmable inputs and will function based 

on  how  they  are  programmed.  Refer  to  Appendix  G(a) 

for programming details.

4.4  Output Relays

The  primary  control  outputs  of  the  LMR  Plus  controller 

are  dry  relay  contacts.  These  relays  are  comprised  of 

two separate "Form C" outputs for Phase Failure, Phase 

Reversal,  Common  Alarm,  Pump  Run,  and  Future  #1. 

The  alarm  relays  are  UL/CSA  rated  at  8A  250Vac  / 

30Vdc.
Each relay has a green LED on the I/O board to indicate 

the relay status. If the LED is "On" the relay is energized 

and "Off" the relay is de-energized.

4.4.1 Relay Functions

Startup

This  is  the  Motor  Start  relay.  It  will  energize  the  Run 

contactor(s), which initiate the motor start.

Acceleration

This relay is used on reduced voltage starting controllers 

only. It will energize after the programmed acceleration 

time  delay.  It  will  then  switch  the  motor  over  to  full 

voltage. 

Phase Failure

This  relay  is  used  for  remote  monitoring  of  a  phase 

failure  alarm  condition.  In  order  to  ensure  dependable 

operation  of  this  relay  it  is  energized  under  normal 

conditions and will de-energize during alarm. This relay 

can also be used to signal the loss of main power in the 

fire pump controller.

Phase Reversal

This  relay  is  used  for  remote  monitoring  of  a  phase 

reversal  condition.  The  phase  reversal  alarm  is  factory 

set in an ABC configuration.

Common Alarm

This relay is used to signal any alarm that the LMR Plus 

controller is alarming on. This relay is energized under 

normal conditions and will de-energize during alarm.

Pump Run

This relay is used for remote monitoring when the pump 

is  running.  When  the  amperage  draw  sensed  by  the 

LMR Plus controller exceeds 20% of the motor full load 

amps, the relay will energize.

Future #1

This relay can be programmed for a number of alarm or 

status  conditions.  Refer  to  Appendix  G(b)  for 

programming details.

5. PROGRAMMING

5.1 Introduction

The LMR Plus controller is fully programmable from the 

device's faceplate. Users can program set points as well 

as other parameters. The time, date, and set points can 

only be changed from the menu system.
The  menu  system  is  broken  down  to  eight  (8)  menu 

groupings.  They  include,  Language,  Regional  Settings, 

Pressure  Settings,  Timer  Values,  Alarm  Set-points, 

Custom  Input/Output,  System  Configuration  Menu,  and 

Main Menu Password.

5.2  Navigation

In  order  to  enter  the  menu  system,  press  the  Menu 

button  on  the  LMR  Plus  faceplate.  If  the  main  menu 

password has been enabled, the user will be required to 

enter the password at this time.
Once in the menu system, the Up and Down arrow keys 

will  provide  navigation  between  each  menu  item.  The 

display  will  show  the previous,  current,  and next menu 

items. The current menu item is located on the middle of 

the four line display.
All  LMR  Plus  controller  programmable  features  and 

associated  set-point  possibilities  are  presented  in 

Table 1.
The following set points are programmable in  the LMR 

Plus controller.

Содержание LMR PLUS

Страница 1: ...EATON LMR Plus Electric Fire Pump Controllers O M Manual IM05805020K Effective September 2013...

Страница 2: ...A MAIN MENU TREE 16 APPENDIX B LANGUAGE MENU TREE 17 APPENDIX C REGIONAL SETTINGS MENU TREE 18 APPENDIX D PRESSURE SETTINGS MENU TREE 19 APPENDIX E TIMER VALUES MENU TREE 20 APPENDIX F ALARM SETPOINT...

Страница 3: ...ross the Line FD40 Part Winding FD50 Primary Resistor FD60 Autotransformer FD70 Wye Delta Star Delta Open Transition FD80 Wye Delta Star Delta Closed Transition FD90 Soft Start and FDM30 Medium Voltag...

Страница 4: ...controller isolated and the Start Pressure and Stop Pressure values programmed energize the controller If the system water pressure is lower than the start pressure the pump will start If the controll...

Страница 5: ...mp is running after receiving a start signal from special starting equipment This is a normally closed contact that is required to be opened to start Emergency Start This green LED will be illuminated...

Страница 6: ...ns When navigating the main display the enter button will allow the user to enter exit the message history statistics and diagnostics When in the menu system the enter button will allow the user to ch...

Страница 7: ...nge 4 2 2 Automatic Start Sequence Automatic start is defined as a low pressure condition deluge valve start or a pump start Whenever the motor is running via an automatic start the motor can automati...

Страница 8: ...tion time delay It will then switch the motor over to full voltage Phase Failure This relay is used for remote monitoring of a phase failure alarm condition In order to ensure dependable operation of...

Страница 9: ...s Pressure Settings Appendix D Pressure Sensor Enabled Enabled Disabled Drain Valve Enabled Enabled Disabled Pressure Start Point 100 PSI 0 500 PSI Pressure Stop Point 110 PSI 0 500 PSI Low Pressure A...

Страница 10: ...ted a delay timer Range 0 30 Seconds Default 10 Seconds must be set The controller will then verify if the input is still active every time the timer times out If the input is still active the timer w...

Страница 11: ...efore alarming on Overvoltage Once the condition no longer exists the alarm will automatically clear Undervoltage UV An Undervoltage setting is built into the controller If the system voltage is below...

Страница 12: ...motor until after an adjustable timer period has elapsed The Load Shed Timer will become active once the Load Shed function is enabled If the emergency input is not active the pump will start normall...

Страница 13: ...h the controller The diagnostics can be viewed on the main display saved to a USB storage device or viewed on the optional embedded webpage In order to view the diagnostics on the display press the up...

Страница 14: ...ing Modbus COM Option must be ordered for this function 7 4 RS232 Serial Port This optional port is used with the optional printer X1 to initiate a print cycle COM Option must be ordered for this func...

Страница 15: ...Note All cells need to be formatted as text Number of Hours Run 3 Column C is used to enter the number of hours the pump has run before the message will appear The format is as follows XXXXX Number o...

Страница 16: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 16 APPENDIX A MAIN MENU TREE...

Страница 17: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 17 www chfire com EATON CORPORATION APPENDIX B LANGUAGE MENU TREE...

Страница 18: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 18 APPENDIX C REGIONAL SETTINGS MENU TREE...

Страница 19: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 19 www chfire com EATON CORPORATION APPENDIX D PRESSURE SETTINGS MENU TREE...

Страница 20: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 20 APPENDIX E TIMER VALUES MENU TREE...

Страница 21: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 21 www chfire com EATON CORPORATION APPENDIX F ALARM SETPOINTS MENU TREE...

Страница 22: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 22 APPENDIX G CUSTOMER INPUT OUTPUT MENU TREE...

Страница 23: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 23 www chfire com EATON CORPORATION APPENDIX G A CUSTOM INPUTS MENU TREE...

Страница 24: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 24 APPENDIX G B CUSTOM OUTPUTS MENU TREE...

Страница 25: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 25 www chfire com EATON CORPORATION APPENDIX G C CUSTOM LIGHTS MENU TREE...

Страница 26: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 26 APPENDIX H MAIN MENU PASSWORD MENU TREE...

Страница 27: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 27 www chfire com EATON CORPORATION APPENDIX J CUSTOM MESSAGE LOAD ACTIVATION...

Страница 28: ...25 30 40 60 75 1 14 1 0 Per CU AL 1 14 2 0 CU AL 40 50 75 100 100 1 4 4 0 Per CU 1 4 350MCM CU AL 75 75 150 200 200 1 3 350MCM Per CU AL 1 4 350MCM CU AL 100 125 200 250 300 2 3 0 250MCM Per CU AL 2 1...

Страница 29: ...shutdown after receiving a low foam level signal LOW PRESSURE The system pressure has dropped below the programmed pressure start point LOW PRESSURE ALARM The system pressure has dropped below the pr...

Страница 30: ...TUP Power has been reapplied to the system and a successful system boot has been completed TRANSDUCER FAILURE The controller has detected that the transducer has failed TRANSDUCER OK The controller ha...

Страница 31: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 31 www chfire com EATON CORPORATION NOTES...

Страница 32: ...o and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and EATON NO WARRANTIES EX...

Отзывы: