background image

O & M Manual IM05805020K

             EATON LMR Plus

Effective September 2013

Electric Fire Pump Controllers

EATON CORPORATION

www.chfire.com

Page 6

3.2.2 Pushbuttons

Silence Alarm - 

When  an  alarm  condition  exists, 

the  alarm  buzzer  will  sound.  If  the  Silence  Alarm 

button is pressed, the alarm buzzer will turn off. If a 

subsequent alarm condition occurs after the silence 

button is pressed, the buzzer will re-sound. Pressing 

the  Silence  Alarm  button  again,  will  silence  the 

buzzer. 

Motor Test - 

 Pressing the ‘Motor Test’ button will 

simulate an automatic start on the controller due to a 

low pressure condition.  
If  the  Drain  Valve  menu  item  is  enabled,  the 

controller will energize the drain valve and wait for 

the  panel  to  be  started.  If,  after  one  minute,  the 

system does not detect a sufficient pressure drop to 

start the controller, the drain valve will de-energize 

and  the  panel  will  alarm.  The  LCD  Display  will 

indicate Motor Test Failure.
If  the  drain  valve  is  disabled,  the  system  will 

simulate a pressure drop and start immediately.
All automatic features of the controller such as Run 

Period Timer and Automatic Shutdown will operate 

as  normal  when  the  Motor  Test  button  is  pressed 

and a low pressure condition is detected.

Data | Print -

 The data, print button allows the user 

to  enter  a  multi-task  menu  where  they  can  initiate 

the  download  of  the  message  history,  system 

diagnostics, system statistics, configuration file to an 

external USB drive, upload custom messages, and 

an additional language. If the optional printer (X1) is 

included with the controller, the user will be able to 

initiate a print cycle through this menu list.

Lamp Test -

 The lamp test button allows the user to 

test all of the LED's on the operator panel. Pressing 

and holding this button will illuminate each LED on 

the operator panel in successive steps.

Reset | Save/Exit -

  The  reset/save/exit  button 

serves two functions. Pressing the reset button will 

reset any alarms that are present on the controller at 

that time. If the alarm condition still exits it will alarm 

again. When the user is in the programming mode, 

pressing the save/exit button will save all of the user 

adjusted  values  and  make  the  recent  changes 

active.

  -

  The  up  arrow  is  used  to  navigate  the  main 

display as well as the menu systems.

  -

 The down arrow is used to navigate the main 

display as well as the menu systems.

 | Ack. -

  The  enter  and  acknowledge  button 

serves  two  functions.  When  navigating  the  main 

display, the enter button will allow the user to enter/

exit the message history, statistics, and diagnostics. 

When  in  the  menu  system,  the  enter  button  will 

allow  the  user  to  change  the  programmed  set 

points, and navigate to the next menu item.

Menu -

  Pressing  the  menu  will  allow  the  user 

access to the programming mode of the controller. 

When  in  the  programming  mode,  the  menu  button 

will serve as a back button to return to the previous 

menu heading.

3.3 Display Board Access Area

The display board is housed in a protective case that is 

mounted on the inside of the controller door. Access to 

communication ports and terminals is possible when the 

controller door is open.

Note:

  To  allow  for  uniform  identification,  the  frame  of 

reference  when  discussing  the  access  area  is  with  the 

panel door open and the user facing the back of the LMR 

Plus controller.
The USB port and I/O board power cable are located on 

the bottom of the chassis. Optional RS232 and RS485 

ports are available.
The  display  contrast  adjustments  can  be  made  via  the 

open potentiometer dial in the back of the chassis.

3.4 Power I/O Board

The  Power  I/O  board  is  used  for  all  connections 

pertaining  to  the  operation  of  the  controller.  From  the 

remote  inputs,  starting  conditions,  and  the  alarm  relay 

outputs.
Refer to the schematic diagram mounted on the inside of 

the controller door for all connection points specific to the 

controller.

3.5 Main Isolating Switch/Circuit Interrupter

The main isolating switch (MIS) is intended for isolating 

an  electric  circuit  from  its  source  of  power.  It  has  no 

interrupting rating and must be externally operable.
The  circuit  interrupter  (CB)  is  used  to  disconnect  a 

running pump motor, if necessary. The CB also provides 

short  circuit  protection  for  the  controller  and  the  pump 

motor and operates in conjunction with the Locked Rotor 

Protector (LRP). In case of a short circuit the CB will trip 

instantaneously.  In  the  case  of  seizure  of  the  pump  or 

motor while starting or running the LRP will trip the CB, 

via a shunt trip, within twenty (20) seconds, as per NFPA 

20 standards.
When  necessary,  a  current  limiter  attachment  may  be 

mounted  on  the  bottom  of  the  CB  to  increase  the 

interrupting capacity.
If  one  or  more  of  the  current  limiter  fuses  blows,  the 

cause  must  be  repaired  immediately  and  new  current 

limiters installed when repairs are complete.
The  isolating  switch  and  circuit  interrupter  are 

interlocked so that the enclosure door cannot be opened 

with  the  handle  in  the  On  position,  except  by  qualified 

electrical personnel. This is accomplished by the use of 

 

 

 

Содержание LMR PLUS

Страница 1: ...EATON LMR Plus Electric Fire Pump Controllers O M Manual IM05805020K Effective September 2013...

Страница 2: ...A MAIN MENU TREE 16 APPENDIX B LANGUAGE MENU TREE 17 APPENDIX C REGIONAL SETTINGS MENU TREE 18 APPENDIX D PRESSURE SETTINGS MENU TREE 19 APPENDIX E TIMER VALUES MENU TREE 20 APPENDIX F ALARM SETPOINT...

Страница 3: ...ross the Line FD40 Part Winding FD50 Primary Resistor FD60 Autotransformer FD70 Wye Delta Star Delta Open Transition FD80 Wye Delta Star Delta Closed Transition FD90 Soft Start and FDM30 Medium Voltag...

Страница 4: ...controller isolated and the Start Pressure and Stop Pressure values programmed energize the controller If the system water pressure is lower than the start pressure the pump will start If the controll...

Страница 5: ...mp is running after receiving a start signal from special starting equipment This is a normally closed contact that is required to be opened to start Emergency Start This green LED will be illuminated...

Страница 6: ...ns When navigating the main display the enter button will allow the user to enter exit the message history statistics and diagnostics When in the menu system the enter button will allow the user to ch...

Страница 7: ...nge 4 2 2 Automatic Start Sequence Automatic start is defined as a low pressure condition deluge valve start or a pump start Whenever the motor is running via an automatic start the motor can automati...

Страница 8: ...tion time delay It will then switch the motor over to full voltage Phase Failure This relay is used for remote monitoring of a phase failure alarm condition In order to ensure dependable operation of...

Страница 9: ...s Pressure Settings Appendix D Pressure Sensor Enabled Enabled Disabled Drain Valve Enabled Enabled Disabled Pressure Start Point 100 PSI 0 500 PSI Pressure Stop Point 110 PSI 0 500 PSI Low Pressure A...

Страница 10: ...ted a delay timer Range 0 30 Seconds Default 10 Seconds must be set The controller will then verify if the input is still active every time the timer times out If the input is still active the timer w...

Страница 11: ...efore alarming on Overvoltage Once the condition no longer exists the alarm will automatically clear Undervoltage UV An Undervoltage setting is built into the controller If the system voltage is below...

Страница 12: ...motor until after an adjustable timer period has elapsed The Load Shed Timer will become active once the Load Shed function is enabled If the emergency input is not active the pump will start normall...

Страница 13: ...h the controller The diagnostics can be viewed on the main display saved to a USB storage device or viewed on the optional embedded webpage In order to view the diagnostics on the display press the up...

Страница 14: ...ing Modbus COM Option must be ordered for this function 7 4 RS232 Serial Port This optional port is used with the optional printer X1 to initiate a print cycle COM Option must be ordered for this func...

Страница 15: ...Note All cells need to be formatted as text Number of Hours Run 3 Column C is used to enter the number of hours the pump has run before the message will appear The format is as follows XXXXX Number o...

Страница 16: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 16 APPENDIX A MAIN MENU TREE...

Страница 17: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 17 www chfire com EATON CORPORATION APPENDIX B LANGUAGE MENU TREE...

Страница 18: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 18 APPENDIX C REGIONAL SETTINGS MENU TREE...

Страница 19: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 19 www chfire com EATON CORPORATION APPENDIX D PRESSURE SETTINGS MENU TREE...

Страница 20: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 20 APPENDIX E TIMER VALUES MENU TREE...

Страница 21: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 21 www chfire com EATON CORPORATION APPENDIX F ALARM SETPOINTS MENU TREE...

Страница 22: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 22 APPENDIX G CUSTOMER INPUT OUTPUT MENU TREE...

Страница 23: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 23 www chfire com EATON CORPORATION APPENDIX G A CUSTOM INPUTS MENU TREE...

Страница 24: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 24 APPENDIX G B CUSTOM OUTPUTS MENU TREE...

Страница 25: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 25 www chfire com EATON CORPORATION APPENDIX G C CUSTOM LIGHTS MENU TREE...

Страница 26: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 26 APPENDIX H MAIN MENU PASSWORD MENU TREE...

Страница 27: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 27 www chfire com EATON CORPORATION APPENDIX J CUSTOM MESSAGE LOAD ACTIVATION...

Страница 28: ...25 30 40 60 75 1 14 1 0 Per CU AL 1 14 2 0 CU AL 40 50 75 100 100 1 4 4 0 Per CU 1 4 350MCM CU AL 75 75 150 200 200 1 3 350MCM Per CU AL 1 4 350MCM CU AL 100 125 200 250 300 2 3 0 250MCM Per CU AL 2 1...

Страница 29: ...shutdown after receiving a low foam level signal LOW PRESSURE The system pressure has dropped below the programmed pressure start point LOW PRESSURE ALARM The system pressure has dropped below the pr...

Страница 30: ...TUP Power has been reapplied to the system and a successful system boot has been completed TRANSDUCER FAILURE The controller has detected that the transducer has failed TRANSDUCER OK The controller ha...

Страница 31: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 31 www chfire com EATON CORPORATION NOTES...

Страница 32: ...o and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and EATON NO WARRANTIES EX...

Отзывы: