O & M Manual IM05805020K

             EATON LMR Plus

Effective September 2013

Electric Fire Pump Controllers

Page 9

www.chfire.com

EATON CORPORATION

Table 1 Programmable Features and Set points

Following  is  a  description  of  each  programmable  set 

point.

Please Enter Password -

  If  the  password  is  enabled, 

the user will be prompted to enter the password at this 

time. If there are no buttons pressed for five (5) seconds, 

the controller will switch back to the automatic mode.

Language -

  Three  (3)  languages  are  offered  as 

standard. They are English, French, or Spanish. A fourth 

language can be added utilizing the USB port. Consult 

Eaton for available languages. Refer to Appendix B for 

programming.

Regional Settings -

 Refer to Appendix C. Following are 

the descriptions of each menu item:

Change Date -

 Factory set, however, this parameter 

allows the user to set the current date.

Change Time -

  Factory  set  to  Mountain  Standard 

Time  (MST).  This  menu  item  allows  the  user  to 

adjust the time to the local time. The clock is of the 

24-hour type.

Description

Factory Default

Range

Main Program - (Appendix A) 
Language (Appendix B)

English

English/French/Spanish

Regional Settings - Appendix C

Change Date

Current Date

Unlimited

Change Time

Current Time (MST)

24 Hours

Pressure Settings - Appendix D

Pressure Sensor

Enabled

Enabled/Disabled

Drain Valve

Enabled

Enabled/Disabled

Pressure Start Point

100 PSI

0-500 PSI

Pressure Stop Point

110 PSI

0-500 PSI

Low Pressure Alarm Point

105 PSI

0-500 PSI

High Pressure Alarm Point

300 PSI

0-500PSI

Auto Shutdown

Automatic

Enabled/Disabled

Proof Pressure Switch

Disabled

Enabled/Disabled (Foam Only)

Low Suction Shutdown (Foam Level)

Disabled

Disabled/Enabled

Pressure Deviation

10 PSI

1-50 PSI

Hourly Pressure Recording

Disabled

Enabled/Disabled

Timer Values - Appendix E

Run Period Timer

10 Minutes

0-45 Minutes

RPT Start Mode

Pump Run

Pump Run/Pressure Stop Point

Acceleration Timer

2 Seconds

0-10 Seconds

Weekly Test Timer

Disabled

7 Days/24 Hours (0-60 Minutes)

Fail To Start

20 Seconds

0-60 Seconds

Fail To Stop

3 Seconds

0-60 Seconds

Sequential Start Timer

Disabled

Disabled / 1-300 Seconds

Alarm Set Points - Appendix F

Phase Rotation

ABC

ABC/CBA

Phase Failure Setup

80%

+20-80%

Overvoltage

+10%

+5-30% / Disabled

Undervoltage

-10%

-5-30% / Disabled

Over Frequency

+5%

+3-10% / Disabled

Under Frequency

-5%

-3-10% / Disabled

Audible Common Alarm

Disabled

Enabled/Disabled

Custom Input/Output - Appendix G

Custom Inputs #1-9

Undefined

Refer to Appendix G(a)

Custom Outputs #1-9

Undefined

Refer to Appendix G(b)

Custom Lights #1-2

Undefined

Refer to Appendix G(c)

Main Menu Password (Appendix H)

Disabled

Enabled/Disabled  -  Any  number  of  four  (4)  button 

combinations from keypad

Содержание LMR PLUS

Страница 1: ...EATON LMR Plus Electric Fire Pump Controllers O M Manual IM05805020K Effective September 2013...

Страница 2: ...A MAIN MENU TREE 16 APPENDIX B LANGUAGE MENU TREE 17 APPENDIX C REGIONAL SETTINGS MENU TREE 18 APPENDIX D PRESSURE SETTINGS MENU TREE 19 APPENDIX E TIMER VALUES MENU TREE 20 APPENDIX F ALARM SETPOINT...

Страница 3: ...ross the Line FD40 Part Winding FD50 Primary Resistor FD60 Autotransformer FD70 Wye Delta Star Delta Open Transition FD80 Wye Delta Star Delta Closed Transition FD90 Soft Start and FDM30 Medium Voltag...

Страница 4: ...controller isolated and the Start Pressure and Stop Pressure values programmed energize the controller If the system water pressure is lower than the start pressure the pump will start If the controll...

Страница 5: ...mp is running after receiving a start signal from special starting equipment This is a normally closed contact that is required to be opened to start Emergency Start This green LED will be illuminated...

Страница 6: ...ns When navigating the main display the enter button will allow the user to enter exit the message history statistics and diagnostics When in the menu system the enter button will allow the user to ch...

Страница 7: ...nge 4 2 2 Automatic Start Sequence Automatic start is defined as a low pressure condition deluge valve start or a pump start Whenever the motor is running via an automatic start the motor can automati...

Страница 8: ...tion time delay It will then switch the motor over to full voltage Phase Failure This relay is used for remote monitoring of a phase failure alarm condition In order to ensure dependable operation of...

Страница 9: ...s Pressure Settings Appendix D Pressure Sensor Enabled Enabled Disabled Drain Valve Enabled Enabled Disabled Pressure Start Point 100 PSI 0 500 PSI Pressure Stop Point 110 PSI 0 500 PSI Low Pressure A...

Страница 10: ...ted a delay timer Range 0 30 Seconds Default 10 Seconds must be set The controller will then verify if the input is still active every time the timer times out If the input is still active the timer w...

Страница 11: ...efore alarming on Overvoltage Once the condition no longer exists the alarm will automatically clear Undervoltage UV An Undervoltage setting is built into the controller If the system voltage is below...

Страница 12: ...motor until after an adjustable timer period has elapsed The Load Shed Timer will become active once the Load Shed function is enabled If the emergency input is not active the pump will start normall...

Страница 13: ...h the controller The diagnostics can be viewed on the main display saved to a USB storage device or viewed on the optional embedded webpage In order to view the diagnostics on the display press the up...

Страница 14: ...ing Modbus COM Option must be ordered for this function 7 4 RS232 Serial Port This optional port is used with the optional printer X1 to initiate a print cycle COM Option must be ordered for this func...

Страница 15: ...Note All cells need to be formatted as text Number of Hours Run 3 Column C is used to enter the number of hours the pump has run before the message will appear The format is as follows XXXXX Number o...

Страница 16: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 16 APPENDIX A MAIN MENU TREE...

Страница 17: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 17 www chfire com EATON CORPORATION APPENDIX B LANGUAGE MENU TREE...

Страница 18: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 18 APPENDIX C REGIONAL SETTINGS MENU TREE...

Страница 19: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 19 www chfire com EATON CORPORATION APPENDIX D PRESSURE SETTINGS MENU TREE...

Страница 20: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 20 APPENDIX E TIMER VALUES MENU TREE...

Страница 21: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 21 www chfire com EATON CORPORATION APPENDIX F ALARM SETPOINTS MENU TREE...

Страница 22: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 22 APPENDIX G CUSTOMER INPUT OUTPUT MENU TREE...

Страница 23: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 23 www chfire com EATON CORPORATION APPENDIX G A CUSTOM INPUTS MENU TREE...

Страница 24: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 24 APPENDIX G B CUSTOM OUTPUTS MENU TREE...

Страница 25: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 25 www chfire com EATON CORPORATION APPENDIX G C CUSTOM LIGHTS MENU TREE...

Страница 26: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 26 APPENDIX H MAIN MENU PASSWORD MENU TREE...

Страница 27: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 27 www chfire com EATON CORPORATION APPENDIX J CUSTOM MESSAGE LOAD ACTIVATION...

Страница 28: ...25 30 40 60 75 1 14 1 0 Per CU AL 1 14 2 0 CU AL 40 50 75 100 100 1 4 4 0 Per CU 1 4 350MCM CU AL 75 75 150 200 200 1 3 350MCM Per CU AL 1 4 350MCM CU AL 100 125 200 250 300 2 3 0 250MCM Per CU AL 2 1...

Страница 29: ...shutdown after receiving a low foam level signal LOW PRESSURE The system pressure has dropped below the programmed pressure start point LOW PRESSURE ALARM The system pressure has dropped below the pr...

Страница 30: ...TUP Power has been reapplied to the system and a successful system boot has been completed TRANSDUCER FAILURE The controller has detected that the transducer has failed TRANSDUCER OK The controller ha...

Страница 31: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 31 www chfire com EATON CORPORATION NOTES...

Страница 32: ...o and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and EATON NO WARRANTIES EX...

Отзывы: