background image

O & M Manual IM05805020K

             EATON LMR Plus

Effective September 2013

Electric Fire Pump Controllers

EATON CORPORATION

www.chfire.com

Page 4

The controller should be located or so protected that it 

will not be damaged by water escaping from pumps or 

pump connections. Current carrying parts of controllers 

shall  be  a  minimum  of  12  inches  (305mm)  above  the 

floor.
Prior to starting, verify all data on the nameplate such as: 

catalog  number,  AC  line  voltage,  horsepower,  and 

frequency.
Inspect  all  electrical  connections,  components,  and 

wiring  for  any  visible  damage.  Correct  as  necessary. 

Ensure  that  all  electrical  connections  are  tightened 

before energizing.
Refer  to  the  wiring  schematic  affixed  to  the  enclosure 

door for all wiring information pertaining to the incoming 

AC power supply and motor wiring.
Install  necessary  conduit  using  proper  methods  and 

tools.
Incoming AC  line  voltage is clearly  marked  L1,  L2,  L3, 

and ground, located at the top of the enclosure.

2.3.1 Wire Sizes

For  control  wiring,  use  #14  AWG  wire  for  all  electrical 

connections.
For power wiring sizes refer to Appendix K.

2.3.2 Electrical Checkout Instructions

To ensure the pump does not start upon energizing the 

controller,  the  interlock  circuit  is  enabled  with  the 

installation  of  a  jumper  between  terminals  39  and  49. 

Energize  the  controller  to  determine  the  status  of  the 

controller.  If  it  is  determined  that  the  controller  will  not 

start the motor, this jumper can be removed.
The  LMR  Plus  controller  is  designed  to  be  phase 

sensitive. L1, L2 & L3 should be connected to A, B & C 

respectively.  Energize  the  controller  by  closing  the 

isolation  switch  (MIS)  and  circuit  breaker  (CB).  If  the 

phases are connected incorrectly, the 'Phase Reversal' 

LED  on  the  alarm  display  will  be  lit.  To  correct  this 

condition,  refer  to  Appendix  F  to  correct  the  phase 

reversal setting. Re-energize the controller.
With  the  controller  energized,  operate  the  'Start' 

pushbutton immediately followed by the 'Stop' button to 

check the rotation of the motor. If the rotation is incorrect 

disconnect  power  and  reverse  connection  of  the  load 

terminals of the motor contactor T1, T2 & T3.

Note: 

On  models  Primary  Resistor  (FD40),  Wye  Delta 

(Star-Delta)  Open  (FD70)  and  Wye  Delta  (Star-Delta) 

Closed (FD80) models, the connection must be changed 

on both contactors.
Adjust the pressure set points detailed in Appendix D.
With the controller isolated and the 'Start Pressure' and 

'Stop  Pressure'  values  programmed,  energize  the 

controller. If the system water pressure is lower than the 

start pressure, the pump will start. If the controller is set 

up for fully automatic operation, the pump will stop when 

the  pressure  is  above  the  stop  point  and  the  running 

period timer (RPT) has completed its timed interval. If the 

controller  is  setup  for  semi-automatic  operation 

(programmed  for  manual  stop  mode),  the  stop 

pushbutton  must  be  operated  to  stop  the  pump.  Note 

that  the  system  pressure  must  be  equal  to  or  greater 

than the programmed stop pressure value, otherwise the 

pump will stop only when the pushbutton is pushed.
The circuit breaker setting is factory set and should not 

be adjusted.
The  running  period  timer  (RPT)  must  be  set  for  a 

minimum  of  ten  (10)  minutes.  Refer  to  Appendix  E  for 

programming of the RPT.
If  the  sequential  start  timer  (SST)  is  required  refer  to 

Appendix  E.  If  not  required  set  the  SST  to  disabled.  If 

required, the lead pump SST should be set to disabled 

and the lag SST to five (5) to ten (10) seconds. If there 

are more than two pumps in the system, allow a ten (10) 

second delay between pumps.
The acceleration timer (AT) is used for reduced voltage 

controllers  only.  The  AT  is  factory  set  based  on  the 

starting method of the controller. If it is found that more 

time is required to allow the pump to come up to speed, 

the timer may be adjusted to suit. Refer to Appendix E 

for programming of the AT.
If  the  Undervoltage/Overvoltage  alarms  are  present, 

check the programmed values by referring to Appendix 

F. If the values are programmed to their maximum and 

the  alarms  continue  to  occur,  check  the  main  voltage 

supply to ensure that the power available is dependable 

as per NFPA, Pamphlet 20 standards.

3. HARDWARE DESCRIPTION

3.1 General

The  purpose  of  this  section  is  to  familiarize  the  reader 

with  the  LMR  Plus  Controller  hardware,  its 

nomenclature, and to list the unit's specifications.

3.2 Front Operator Panel

The front operator panel, depending on the installation, 

is normally accessible from the outside of the door. The 

front panel provides a means to:

Alert the user to specific conditions

Program the controller

Set and monitor the operating parameters

The LMR Plus Controller front panel serves two primary 

functions: output and input. The output function consists 

of:

A four-line, 40 character LCD display module

Twenty  LED  outputs:  Power  On,  Pump  Running, 

Local Start, Remote Start, Deluge Valve, Emergency 

Start, Interlock On, Low Pressure, Phase Reversal, 

Содержание LMR PLUS

Страница 1: ...EATON LMR Plus Electric Fire Pump Controllers O M Manual IM05805020K Effective September 2013...

Страница 2: ...A MAIN MENU TREE 16 APPENDIX B LANGUAGE MENU TREE 17 APPENDIX C REGIONAL SETTINGS MENU TREE 18 APPENDIX D PRESSURE SETTINGS MENU TREE 19 APPENDIX E TIMER VALUES MENU TREE 20 APPENDIX F ALARM SETPOINT...

Страница 3: ...ross the Line FD40 Part Winding FD50 Primary Resistor FD60 Autotransformer FD70 Wye Delta Star Delta Open Transition FD80 Wye Delta Star Delta Closed Transition FD90 Soft Start and FDM30 Medium Voltag...

Страница 4: ...controller isolated and the Start Pressure and Stop Pressure values programmed energize the controller If the system water pressure is lower than the start pressure the pump will start If the controll...

Страница 5: ...mp is running after receiving a start signal from special starting equipment This is a normally closed contact that is required to be opened to start Emergency Start This green LED will be illuminated...

Страница 6: ...ns When navigating the main display the enter button will allow the user to enter exit the message history statistics and diagnostics When in the menu system the enter button will allow the user to ch...

Страница 7: ...nge 4 2 2 Automatic Start Sequence Automatic start is defined as a low pressure condition deluge valve start or a pump start Whenever the motor is running via an automatic start the motor can automati...

Страница 8: ...tion time delay It will then switch the motor over to full voltage Phase Failure This relay is used for remote monitoring of a phase failure alarm condition In order to ensure dependable operation of...

Страница 9: ...s Pressure Settings Appendix D Pressure Sensor Enabled Enabled Disabled Drain Valve Enabled Enabled Disabled Pressure Start Point 100 PSI 0 500 PSI Pressure Stop Point 110 PSI 0 500 PSI Low Pressure A...

Страница 10: ...ted a delay timer Range 0 30 Seconds Default 10 Seconds must be set The controller will then verify if the input is still active every time the timer times out If the input is still active the timer w...

Страница 11: ...efore alarming on Overvoltage Once the condition no longer exists the alarm will automatically clear Undervoltage UV An Undervoltage setting is built into the controller If the system voltage is below...

Страница 12: ...motor until after an adjustable timer period has elapsed The Load Shed Timer will become active once the Load Shed function is enabled If the emergency input is not active the pump will start normall...

Страница 13: ...h the controller The diagnostics can be viewed on the main display saved to a USB storage device or viewed on the optional embedded webpage In order to view the diagnostics on the display press the up...

Страница 14: ...ing Modbus COM Option must be ordered for this function 7 4 RS232 Serial Port This optional port is used with the optional printer X1 to initiate a print cycle COM Option must be ordered for this func...

Страница 15: ...Note All cells need to be formatted as text Number of Hours Run 3 Column C is used to enter the number of hours the pump has run before the message will appear The format is as follows XXXXX Number o...

Страница 16: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 16 APPENDIX A MAIN MENU TREE...

Страница 17: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 17 www chfire com EATON CORPORATION APPENDIX B LANGUAGE MENU TREE...

Страница 18: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 18 APPENDIX C REGIONAL SETTINGS MENU TREE...

Страница 19: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 19 www chfire com EATON CORPORATION APPENDIX D PRESSURE SETTINGS MENU TREE...

Страница 20: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 20 APPENDIX E TIMER VALUES MENU TREE...

Страница 21: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 21 www chfire com EATON CORPORATION APPENDIX F ALARM SETPOINTS MENU TREE...

Страница 22: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 22 APPENDIX G CUSTOMER INPUT OUTPUT MENU TREE...

Страница 23: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 23 www chfire com EATON CORPORATION APPENDIX G A CUSTOM INPUTS MENU TREE...

Страница 24: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 24 APPENDIX G B CUSTOM OUTPUTS MENU TREE...

Страница 25: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 25 www chfire com EATON CORPORATION APPENDIX G C CUSTOM LIGHTS MENU TREE...

Страница 26: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 26 APPENDIX H MAIN MENU PASSWORD MENU TREE...

Страница 27: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 27 www chfire com EATON CORPORATION APPENDIX J CUSTOM MESSAGE LOAD ACTIVATION...

Страница 28: ...25 30 40 60 75 1 14 1 0 Per CU AL 1 14 2 0 CU AL 40 50 75 100 100 1 4 4 0 Per CU 1 4 350MCM CU AL 75 75 150 200 200 1 3 350MCM Per CU AL 1 4 350MCM CU AL 100 125 200 250 300 2 3 0 250MCM Per CU AL 2 1...

Страница 29: ...shutdown after receiving a low foam level signal LOW PRESSURE The system pressure has dropped below the programmed pressure start point LOW PRESSURE ALARM The system pressure has dropped below the pr...

Страница 30: ...TUP Power has been reapplied to the system and a successful system boot has been completed TRANSDUCER FAILURE The controller has detected that the transducer has failed TRANSDUCER OK The controller ha...

Страница 31: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 31 www chfire com EATON CORPORATION NOTES...

Страница 32: ...o and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and EATON NO WARRANTIES EX...

Отзывы: