background image

O & M Manual IM05805020K

             EATON LMR Plus

Effective September 2013

Electric Fire Pump Controllers

EATON CORPORATION

www.chfire.com

Page 10

Pressure Settings -

 Refer to Appendix D. Following are 

the descriptions of each menu item:

Pressure Sensor - 

Some  applications  do  not 

require  a  pressure  sensor  to  sense  the  system 

pressure  in  order  to  start  the  pump  motor  when 

required. In order to accomplish this. The pressure 

sensor  can  be  disabled  through  this  menu  item. 

Once  disabled,  the  pressure  start  point,  pressure 

stop  point,  low  pressure  alarm,  and  high  pressure 

alarm  set-points  will  be  removed  from  the  menu 

system. Refer to 4.3 for the Pump Start input to use 

instead of the pressure sensor.

Pressure Start Point - 

The  value  programmed 

determines  at  which  pressure  the  controller  will 

initiate a start sequence.

Pressure Stop Point - 

The  value  programmed 

determines  the  pressure  the  system  must  reach 

before the controller will automatically stop the fire 

pump  motor,  via  the  running  period  timer.  If  the 

system pressure does not exceed the programmed 

Pressure  Stop  Point,  the  fire  pump  motor  will 

continue to run. (Auto shutdown only)

Low Pressure Alarm -

 A low pressure alarm point 

can  be  selected  that  will  be  recorded  in  the 

controller's history.

High Pressure Alarm -

 A high pressure alarm point 

can  be  selected  that  will  be  recorded  in  the 

controller's history.

Auto Shutdown -

 The auto shutdown mode is user 

selectable.  If the auto shutdown mode is disabled, 

the pump motor must be stopped via the local stop 

pushbutton, whether or not the motor started via an 

automatic  start.    If  the  auto  shutdown  mode  is 

enabled,  the  controller  will  stop  the  pump  motor 

automatically  after  all  starting  causes  have  been 

returned to normal and the running period timer has 

timed out.

Proof Pressure Switch - 

An  external  pressure 

switch will activate input # 1, terminal 40. This menu 

item  will  only  be  active  when  the  controller  is 

programmed for a Foam Pump Controller.

Low Suction Shutdown/Foam Level -

  The 

controller can be programmed to shutdown when a 

low  suction  condition  is  present.  If  this  is  desired, 

the  user  will  select  Enabled.  There  will  also  be  a 

shutdown delay timer built in (Range: 0-30 Seconds, 

Default:  10  Seconds)  along  with  the  selection  of 

either a Manual or Automatic reset. If Manual Reset 

is selected, the Ack./Alarm button on the faceplate 

must be activated to reset the alarm. If an Automatic 

Reset (default reset mode) is selected, a delay timer 

(Range: 0-30 Seconds, Default: 10 Seconds) must 

be set. The controller will then verify if the input is 

still active, every time the timer times out. If the input 

is  still  active  the  timer  will  reset  and  count  down 

again. Once the input has been removed, the timer 

will start timing. Once the timer has finished timing, 

out  the  controller  will  return  to  the  automatic  run 

mode. When the shutdown delay timer is timing, the 

time left on the timer will be displayed on the fourth 

line of the display. When the controller is shutdown 

on  Low  Suction,  the  display  will  read  Low  Suction 

Shutdown. The display will also show the automatic 

reset  time  delay  when  timing.  Low  Suction 

Shutdown  will  not  work  on  Local  Starts,  Remote 

Starts, or Emergency Starts.

Pressure Deviation -

  A  pressure  setting  may  be 

selected, such that any change in pressure greater 

than this setting, will record the pressure fluctuation 

in the alarm memory.

Hourly Pressure Recording -

  The  controller  can 

be set so that it will take a pressure reading every 

hour on the hour. If this feature is not required it can 

be turned off by selecting Disabled.

Timer Values -

  Refer  to  Figure  #6.  Following  are  the 

descriptions or each menu item:

Run Period Timer (RPT) -

 The run period timer is 

used  to  automatically  stop  the  controller  after  a 

programmed time. It can be programmed to operate 

based on either of two separate conditions, the stop 

pressure point or when the pump has started to run. 

If  the  RPT  is  programmed  to  start  at  the  Stop 

Pressure, the timer will start timing once the system 

pressure  has  reached  the  programmed  Stop 

Pressure  Point.  If  the  RPT  is  programmed  to  start 

timing once the pump is running then the timer will 

start timing once the pump  has reached a running 

condition.  If  Automatic  Shutdown  is  enabled,  the 

RPT will not  be  active. It  will not start on Remote, 

Local, and Emergency Starts. While it is timing the 

amount of time left on the timer will be displayed on 

the fourth line of the display.

RPT Start Mode -

 The point at which the run period 

timer  starts  timing  is  programmable.  If  it  is 

programmed  to  start  timing  after  the  pump  has 

started,  the  RPT  will  start  timing  once  20%  of  the 

motor FLA has been reached. If it is programmed to 

start timing once the Stop Pressure Point has been 

reached, the RPT will start timing when the system 

pressure has risen above the programmed Pressure 

Stop Point.

ATTENTION

NFPA 20, SECTION 2-9.9, SPECIFICALLY 
PROHIBITS THE INSTALLATION OF ANY DEVICE 
IN THE SUCTION PIPING THAT WILL RESTRICT 
STARTING OR STOPPING OF THE FIRE PUMP. 
EATON CORPORATION ASSUMES NO LIABILITY 
WHEN THIS FUNCTION IS USED.

Содержание LMR PLUS

Страница 1: ...EATON LMR Plus Electric Fire Pump Controllers O M Manual IM05805020K Effective September 2013...

Страница 2: ...A MAIN MENU TREE 16 APPENDIX B LANGUAGE MENU TREE 17 APPENDIX C REGIONAL SETTINGS MENU TREE 18 APPENDIX D PRESSURE SETTINGS MENU TREE 19 APPENDIX E TIMER VALUES MENU TREE 20 APPENDIX F ALARM SETPOINT...

Страница 3: ...ross the Line FD40 Part Winding FD50 Primary Resistor FD60 Autotransformer FD70 Wye Delta Star Delta Open Transition FD80 Wye Delta Star Delta Closed Transition FD90 Soft Start and FDM30 Medium Voltag...

Страница 4: ...controller isolated and the Start Pressure and Stop Pressure values programmed energize the controller If the system water pressure is lower than the start pressure the pump will start If the controll...

Страница 5: ...mp is running after receiving a start signal from special starting equipment This is a normally closed contact that is required to be opened to start Emergency Start This green LED will be illuminated...

Страница 6: ...ns When navigating the main display the enter button will allow the user to enter exit the message history statistics and diagnostics When in the menu system the enter button will allow the user to ch...

Страница 7: ...nge 4 2 2 Automatic Start Sequence Automatic start is defined as a low pressure condition deluge valve start or a pump start Whenever the motor is running via an automatic start the motor can automati...

Страница 8: ...tion time delay It will then switch the motor over to full voltage Phase Failure This relay is used for remote monitoring of a phase failure alarm condition In order to ensure dependable operation of...

Страница 9: ...s Pressure Settings Appendix D Pressure Sensor Enabled Enabled Disabled Drain Valve Enabled Enabled Disabled Pressure Start Point 100 PSI 0 500 PSI Pressure Stop Point 110 PSI 0 500 PSI Low Pressure A...

Страница 10: ...ted a delay timer Range 0 30 Seconds Default 10 Seconds must be set The controller will then verify if the input is still active every time the timer times out If the input is still active the timer w...

Страница 11: ...efore alarming on Overvoltage Once the condition no longer exists the alarm will automatically clear Undervoltage UV An Undervoltage setting is built into the controller If the system voltage is below...

Страница 12: ...motor until after an adjustable timer period has elapsed The Load Shed Timer will become active once the Load Shed function is enabled If the emergency input is not active the pump will start normall...

Страница 13: ...h the controller The diagnostics can be viewed on the main display saved to a USB storage device or viewed on the optional embedded webpage In order to view the diagnostics on the display press the up...

Страница 14: ...ing Modbus COM Option must be ordered for this function 7 4 RS232 Serial Port This optional port is used with the optional printer X1 to initiate a print cycle COM Option must be ordered for this func...

Страница 15: ...Note All cells need to be formatted as text Number of Hours Run 3 Column C is used to enter the number of hours the pump has run before the message will appear The format is as follows XXXXX Number o...

Страница 16: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 16 APPENDIX A MAIN MENU TREE...

Страница 17: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 17 www chfire com EATON CORPORATION APPENDIX B LANGUAGE MENU TREE...

Страница 18: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 18 APPENDIX C REGIONAL SETTINGS MENU TREE...

Страница 19: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 19 www chfire com EATON CORPORATION APPENDIX D PRESSURE SETTINGS MENU TREE...

Страница 20: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 20 APPENDIX E TIMER VALUES MENU TREE...

Страница 21: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 21 www chfire com EATON CORPORATION APPENDIX F ALARM SETPOINTS MENU TREE...

Страница 22: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 22 APPENDIX G CUSTOMER INPUT OUTPUT MENU TREE...

Страница 23: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 23 www chfire com EATON CORPORATION APPENDIX G A CUSTOM INPUTS MENU TREE...

Страница 24: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 24 APPENDIX G B CUSTOM OUTPUTS MENU TREE...

Страница 25: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 25 www chfire com EATON CORPORATION APPENDIX G C CUSTOM LIGHTS MENU TREE...

Страница 26: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 26 APPENDIX H MAIN MENU PASSWORD MENU TREE...

Страница 27: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 27 www chfire com EATON CORPORATION APPENDIX J CUSTOM MESSAGE LOAD ACTIVATION...

Страница 28: ...25 30 40 60 75 1 14 1 0 Per CU AL 1 14 2 0 CU AL 40 50 75 100 100 1 4 4 0 Per CU 1 4 350MCM CU AL 75 75 150 200 200 1 3 350MCM Per CU AL 1 4 350MCM CU AL 100 125 200 250 300 2 3 0 250MCM Per CU AL 2 1...

Страница 29: ...shutdown after receiving a low foam level signal LOW PRESSURE The system pressure has dropped below the programmed pressure start point LOW PRESSURE ALARM The system pressure has dropped below the pr...

Страница 30: ...TUP Power has been reapplied to the system and a successful system boot has been completed TRANSDUCER FAILURE The controller has detected that the transducer has failed TRANSDUCER OK The controller ha...

Страница 31: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 31 www chfire com EATON CORPORATION NOTES...

Страница 32: ...o and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and EATON NO WARRANTIES EX...

Отзывы: