background image

O & M Manual IM05805020K

             EATON LMR Plus

Effective September 2013

Electric Fire Pump Controllers

Page 11

www.chfire.com

EATON CORPORATION

Acceleration Timer (AT) -

  The  acceleration  timer 

can be programmed to allow the controller to run in 

a  reduced  voltage  state  for  a  period  of  time.  This 

timer  will start  timing  once  a  start  signal  has  been 

received and the startup relay has energized.

Weekly Test Timer -

  A  Weekly  Timer  can  be 

programmed that will automatically start and run the 

fire  pump  motor.  The  Weekly  Timer  is  set  by 

adjusting  the  day,  hour,  and  minute  of  the  desired 

weekly run time, the length of time that this test shall 

be performed, and a Test Interval (TI) (Range 1-52 

Weeks) that will run the test every TI weeks. While 

the  weekly  test  timer  is  timing,  the  remaining  time 

will be displayed on the fourth line of the display.

Fail To Start Timer (FTS) -

 The controller will verify 

that  the  motor  has  reached  an  amperage  rating 

greater that 20% of the programmed motor full load 

amps  when  the  pump  is  running.  If  the  amperage 

has not reached 20% of the motor FLA after the Fail 

To Start timer has timed out the Fail to Start alarm 

will be generated. 

Fail To Stop Timer -

 The controller will verify that 

the  amperage  draw  from  the  motor  has  dropped 

below 20% of the programmed motor full load amps 

when there is a call to stop. If the amperage has not 

dropped below 20% of the motor FLA, after the Fail 

To Stop timer has timed out, the Fail to Stop alarm 

will be generated.

Sequential Start Timer (SST) -

 The SST can be set 

to  delay  the  starting  of  the  pump  when  a  low-

pressure condition exists. If, during the timing of the 

sequential  timer,  the  pressure  rises  above  the 

pressure  start  point,  the  timer  will  stop  timing  and 

the  starting  sequence  will  discontinue.  When  the 

SST is timing, the time left will be displayed on the 

fourth line of the display. The SST will not work on 

Remote starts, Local starts and Emergency starts.

Alarm Set Points -

  Following  are  the  descriptions  for 

each menu item:

Phase Rotation -

 The user will be able to change 

the  Phase  Rotation  that  the  program  will  base  the 

Phase Reversal alarm on.

Overvoltage (OV) -

 An Overvoltage setting is built 

into the controller. If the system voltage is above this 

percentage setting, an alarm will be activated. There 

is  a  one  (1)  second  delay  before  alarming  on 

Overvoltage.  Once  the  condition  no  longer  exists, 

the alarm will automatically clear.

Undervoltage (UV) -

  An  Undervoltage  setting  is 

built  into  the  controller.  If  the  system  voltage  is 

below  this  percentage  setting,  an  alarm  will  be 

activated.  There  is  a  one  (1)  second  delay  before 

alarming  on  Undervoltage.  Once  the  condition  no 

longer exists, the alarm will automatically clear.

Over Frequency (OF) -

 An Over Frequency setting 

is built into the controller. If the system frequency is 

above  this  percentage  setting,  an  alarm  will  be 

activated.  Once  the  condition  no  longer  exists  the 

alarm  will  automatically  clear.  There  is  a  three  (3) 

second delay before alarming on Over Frequency.

Under Frequency (UF) -

  An  Under  Frequency 

setting  is  built  into  the  controller.  If  the  system 

frequency is below this percentage setting, an alarm 

will be activated. Once the condition no longer exists 

the  alarm  will  automatically  clear.  There  is  a  three 

(3)  second  delay  before  alarming  on  Under 

Frequency.

Custom Input/Output -

 Refer to Appendix G. Following 

are the descriptions or each menu item:

Custom Inputs -

 The optional inputs have the ability to 

be  programmed  for  predetermined  values  or  custom 

values. The Custom Input Menu will display each input, 

what it is programmed for and if there are any associated 

optional relays and / or lights linked to the input. Refer to 

Table  2  Generic  Custom  Input  Labels  for  the  generic 

values the optional inputs can be programmed for. When 

this input is received a message will be stored in memory 

using the programmed label.

Table 2 Generic Custom Input Labels

Label -

 If the input label is set to Custom Input, this 

menu item will become active and allow the user to 

enter  the  desired  input  name  in.  The  label  will  be 

limited to 20 characters in length and will include all 

standard ASCII characters.

Energize Common Alarm -

  If  required,  the 

common alarm relay (3CR) can be programmed to 

change  states  when  this  input  is  received.  Default 

value is Disabled.

Link to Relay - 

All inputs can be linked to an output 

relay. If the relay has been linked to another input or 

is programmed for another alarm, the program will 

show  that  the  output  is  programmed  for  another 

alarm  and  ask  if  the  relay  should  be  reassigned. 

Default value is Disabled.

Input

Custom Input #1
Relief Valve Discharge
Low Oil Pressure
Proof Pressure Switch
Emergency Switch Open
Jockey Pump Run
Secondary Pump Run
Low Reservoir
High Reservoir
Pump Room Door Open
Supervisory Power Fail
Generator Disconnected

Содержание LMR PLUS

Страница 1: ...EATON LMR Plus Electric Fire Pump Controllers O M Manual IM05805020K Effective September 2013...

Страница 2: ...A MAIN MENU TREE 16 APPENDIX B LANGUAGE MENU TREE 17 APPENDIX C REGIONAL SETTINGS MENU TREE 18 APPENDIX D PRESSURE SETTINGS MENU TREE 19 APPENDIX E TIMER VALUES MENU TREE 20 APPENDIX F ALARM SETPOINT...

Страница 3: ...ross the Line FD40 Part Winding FD50 Primary Resistor FD60 Autotransformer FD70 Wye Delta Star Delta Open Transition FD80 Wye Delta Star Delta Closed Transition FD90 Soft Start and FDM30 Medium Voltag...

Страница 4: ...controller isolated and the Start Pressure and Stop Pressure values programmed energize the controller If the system water pressure is lower than the start pressure the pump will start If the controll...

Страница 5: ...mp is running after receiving a start signal from special starting equipment This is a normally closed contact that is required to be opened to start Emergency Start This green LED will be illuminated...

Страница 6: ...ns When navigating the main display the enter button will allow the user to enter exit the message history statistics and diagnostics When in the menu system the enter button will allow the user to ch...

Страница 7: ...nge 4 2 2 Automatic Start Sequence Automatic start is defined as a low pressure condition deluge valve start or a pump start Whenever the motor is running via an automatic start the motor can automati...

Страница 8: ...tion time delay It will then switch the motor over to full voltage Phase Failure This relay is used for remote monitoring of a phase failure alarm condition In order to ensure dependable operation of...

Страница 9: ...s Pressure Settings Appendix D Pressure Sensor Enabled Enabled Disabled Drain Valve Enabled Enabled Disabled Pressure Start Point 100 PSI 0 500 PSI Pressure Stop Point 110 PSI 0 500 PSI Low Pressure A...

Страница 10: ...ted a delay timer Range 0 30 Seconds Default 10 Seconds must be set The controller will then verify if the input is still active every time the timer times out If the input is still active the timer w...

Страница 11: ...efore alarming on Overvoltage Once the condition no longer exists the alarm will automatically clear Undervoltage UV An Undervoltage setting is built into the controller If the system voltage is below...

Страница 12: ...motor until after an adjustable timer period has elapsed The Load Shed Timer will become active once the Load Shed function is enabled If the emergency input is not active the pump will start normall...

Страница 13: ...h the controller The diagnostics can be viewed on the main display saved to a USB storage device or viewed on the optional embedded webpage In order to view the diagnostics on the display press the up...

Страница 14: ...ing Modbus COM Option must be ordered for this function 7 4 RS232 Serial Port This optional port is used with the optional printer X1 to initiate a print cycle COM Option must be ordered for this func...

Страница 15: ...Note All cells need to be formatted as text Number of Hours Run 3 Column C is used to enter the number of hours the pump has run before the message will appear The format is as follows XXXXX Number o...

Страница 16: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 16 APPENDIX A MAIN MENU TREE...

Страница 17: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 17 www chfire com EATON CORPORATION APPENDIX B LANGUAGE MENU TREE...

Страница 18: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 18 APPENDIX C REGIONAL SETTINGS MENU TREE...

Страница 19: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 19 www chfire com EATON CORPORATION APPENDIX D PRESSURE SETTINGS MENU TREE...

Страница 20: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 20 APPENDIX E TIMER VALUES MENU TREE...

Страница 21: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 21 www chfire com EATON CORPORATION APPENDIX F ALARM SETPOINTS MENU TREE...

Страница 22: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 22 APPENDIX G CUSTOMER INPUT OUTPUT MENU TREE...

Страница 23: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 23 www chfire com EATON CORPORATION APPENDIX G A CUSTOM INPUTS MENU TREE...

Страница 24: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 24 APPENDIX G B CUSTOM OUTPUTS MENU TREE...

Страница 25: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 25 www chfire com EATON CORPORATION APPENDIX G C CUSTOM LIGHTS MENU TREE...

Страница 26: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers EATON CORPORATION www chfire com Page 26 APPENDIX H MAIN MENU PASSWORD MENU TREE...

Страница 27: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 27 www chfire com EATON CORPORATION APPENDIX J CUSTOM MESSAGE LOAD ACTIVATION...

Страница 28: ...25 30 40 60 75 1 14 1 0 Per CU AL 1 14 2 0 CU AL 40 50 75 100 100 1 4 4 0 Per CU 1 4 350MCM CU AL 75 75 150 200 200 1 3 350MCM Per CU AL 1 4 350MCM CU AL 100 125 200 250 300 2 3 0 250MCM Per CU AL 2 1...

Страница 29: ...shutdown after receiving a low foam level signal LOW PRESSURE The system pressure has dropped below the programmed pressure start point LOW PRESSURE ALARM The system pressure has dropped below the pr...

Страница 30: ...TUP Power has been reapplied to the system and a successful system boot has been completed TRANSDUCER FAILURE The controller has detected that the transducer has failed TRANSDUCER OK The controller ha...

Страница 31: ...O M Manual IM05805020K EATON LMR Plus Effective September 2013 Electric Fire Pump Controllers Page 31 www chfire com EATON CORPORATION NOTES...

Страница 32: ...o and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and EATON NO WARRANTIES EX...

Отзывы: