Outputs Menu
Page 68
Courtesy Light (45)
Active when the entry or exit timer is running. The control unit activates this output
when the entry or exit time starts, and deactivates the output 10 seconds after the
entry or exit time stops.
Installer on Site (46)
The control unit activates the output when an installer enters the Installer menu, and
deactivates the output once the installer has exited the Installer menu.
Duress Code (47)
Active when a user keys in a Duress code, and deactivates the output when a user or
engineer resets the system.
HUA Confirm (48)
(Not available on EU control units. Operates only when BS8243 is enabled.)
Active when either of the following occurs:
a) Users have activated two separate Hold Up Devices (HUDs) within the HUA
confirmation time.
b) A HUD and a tamper are activated (in either order) within the HUA confirmation
time.
Note that the HUDs (and tampers) must both be in the same partitions as the output.
The control unit deactivates the output when a user or engineer resets the system.
Lockset Unlocked (49)
The control unit activates the output when the Lock Set zone is activated, and
deactivates the output when a Lock Set zone is deactivated.
Burg Confirm timer (50)
(Not available on EU control units. Operates only when BS8243 or DD243 is
enabled.)
Active when a Burg confirmation timer is running. Inactive when the timer stops.
HUA confirm timer (51)
(Not available on EU control units. Operates only when BS8243 is enabled.)
Active when an HUA confirmation timer is running. Inactive when the timer stops.
Rearmed (52)
In a part-setting system, the control unit activates the output if the system re-arms at
least once after the user armed it.
If
Confirmation Mode
(page 86) is set to BS8243 or DD243, the control unit activates
the output as it rearms the system after the confirmation timer expires.
If
Confirmation Mode
is set to Basic, the control unit activates the output as it rearms
the system when the bell/siren time expires.
The control unit deactivates the output when a user or installer resets the
system/partition.
Burg Confirmed Alarm (53)
(Not available on EU control units. Operates only when BS8243 is enabled.)
Active when either of the following occurs:
a) Two separate Normal Alarm (Burgs) have activated in the same partition within the
confirmation time.
b) A Normal Alarm and Tamper are active (in any order) from the same partition
within the confirmation time.